background image

RO

 

EN 

 

35 

GROUP 0 - PRESSURE PARAMETERS 

 

0.0 – Pressure set point:

 this parameter enables entry of the device set point. It is a constant pressure 

value required by the system (maximum pressure). During its operation, 

Nettuno

 adjusts the electric pump 

revs  to  adapt  them  to  the  actual  demand  from  the  utilities,  therefore  maintaining  a  constant  system 
pressure

.

 The set value must be below the maximum delivery pressure of the pump, to ensure specific 

modulation of the pump itself and consequent energy savings.  

0.1 - Pump start-up Delta P:

 

this parameter sets the the negative pressure delta compared to the pump 

start-up set point. On opening of any type of utility, the pump will not start-up until the system pressure 
has fallen below the set point by a value equal to the delta set in this parameter. After the motor is started 
up, the rotation speed is controlled to maintain the pressure value as close as possible to that set in the 

pressure set point parameter. The minimum differential settable between Pmax and Pmin is 0.3 Bar, with the recommended value being at 
least 0.5 Bar. 

0.2  –  Dry  running  pressure:

  set  a  minimum  pressure  value,  below  which  the  dry  running  protection 

device trips due to lack of water. In the case of pump operation at maximum speed, if the pressure in the 
system falls below this value, the inverter stops the motor. To ensure correct operation of the protection 
device, the settable value must never be higher than the set start-up pressure (obtained from the difference 

between the set point and the deltaP values described above). Operation of the protection device should be tested after installation. Also 
take into account the water column on outlet, if present.

 

 
0.3 - Limit pressure: 

this parameter sets the limit for the over-pressure protection to intervene. 

Tripping of the over-pressure protection stops operation of the inverter until it is reset by the user. 
 
 

0.4 – Pressure 2 set point: 

this parameter enables entry of the secondary set point of the device. When 

the I/O board input is closed externally, the pressure value set in this parameter becomes the new set point 
, according to which 

Nettuno 

regulates the revs of the electric pump (see also parameter 3.1). 

 

0.5 - Immediate stop Delta P: 

this parameter sets the positive pressure delta compared to the set point  

for immediate shutdown of the pump. During normal operation, when the valves close, the pump stops 
after a time set in the parameter "stop delay". In any event, if the system pressure exceeds the Pmax value 
of  a  delta  greater  than  the  value  set  in  this  parameter,  the  pump  will  stop  immediately  to  avoid 
overpressure which may damage the system. 

 

 0.6 - Unit of measurement: 

select the unit of measurement in BAR or PSI

 

 

 

0.7 – Sensor full scale: 

this defines the full scale of the connected pressure sensor. It is compatible with 

pressure  sensors  from  0-6  bar  up  to  0-16  bar  or  from  0-100  PSI  up  to  0-250  PSI,  with  current  signal 
4÷20mA.

 

 

 
 

GROUP 1 : MOTOR PARAMETERS 

 
 

1.0  –  Motor  current: 

  this  parameter  enables  entry  of  the  maximum  current  absorbed  by  the  electric 

pump in routine conditions, to enable shut-down of the motor in the event of excessive absorption.   Shut-
down occurs also if the current is unbalanced between phases by more than 25% with respect to the set 
maximum value. 
The trip time of the current overload safety device is inversely proportional to the entity of the overload 

in progress; therefore, a slight overload will lead to a more delayed trip time while a more significant overload will accelerate the trip time.  

 

1.1 - Direction of rotation: 

this screen enables the user to invert the direction of rotation of the electric 

pump without modification to the electric motor wiring. To modify the direction of rotation of the motor, 
use keys "+" and "-"; the direction indicated by the arrow has a purely indicative value and does not reflect 
the actual sense of rotation, which must be verified by the installer. 

 

1.2 - Minimum frequency: 

this parameter defines the minimum frequency at which the pump is started 

up and defines the end of the ramp for shutdown. For three-phase pumps a value of 25Hz is advised. Also 
consult the information supplied by the manufacturer of the electric pump to determine at what minimum 
frequency value the connected electric motor can operate.  

0.0    Pressure 

setpoint 3.0 BAR 

0.1 DeltaP start   

pump   1.0 BAR 

0.2 Dry Running 

Press.  0.5 BAR 

0.3  Over  press. 

Limit  16.0 BAR 

0.4 Pressure set 

point2  3.0 BAR 

0.5  DeltaP  stop 

immed.  1.5 BAR 

0.6  Measurement 

unit      BAR 

0.7  Pres.Sens. 

Scale 16.0

 

BAR

 

1.0 Motor rated 

Current    0.5A 

1.1 Motor rotat. 

Direct

   

-->

 

1.2  Minimum   

Freq.   25 Hz 

Содержание NETTUNO 3P-13A

Страница 1: ...RO EN Rel 3 2 07 2018 3P 13A Nettuno 3P 9A 3P 6A...

Страница 2: ...pecializat capabil s n eleag pe deplin ce este explicat n acest manual de instruc iuni Toate opera iunile efectuate prin scoaterea capacului dispozitivului trebuie efectuate cu sursa de alimentare dec...

Страница 3: ...t n cazul lipsei de ap n aspira ie Resetare automat n cazul opririi pentru func ionare uscat capabil s rezolve n mod autonom starea de eroare Control eficient al scurgerilor pentru protec ia pompei n...

Страница 4: ...a evita riscul de scufundare n caz de inunda ii Dispozitivul nu trebuie instalat n spa ii nchise care pot reduce ventila ia i prin urmare r cirea invertorului MONTAJ PE PERETE Nettuno poate fi instal...

Страница 5: ...bine fixat pe eav i nu se 4 uruburi din dotare Consulta i fig 6 pentru selectarea orificiilor roti 3 Preasambla i uruburile de fixare de pe partea din spate a 4 Introduce i Nettuno pe suport permi nd...

Страница 6: ...ta de aspira ie atunci c nd pompa este oprit n cazul instal rii multiple se recomand instalarea unei supape pe conducta de aspira ie pentru fiecare pomp ATEN IE c nd pompa se opre te conductele sunt n...

Страница 7: ...t al acestuia sau de personal calificat pentru a preveni riscurile la proprietate sau persoane Introduce i cablurile electrice n presetupele corespunz toare respect nd ordinea corect de montare a tutu...

Страница 8: ...ntotdeauna n amonte de invertor un dispozitiv care s asigure deconectarea de la re eaua electric n mod omnipolar cu o distan de deschidere a contactelor de minimum 3mm nainte de a efectua conexiunea...

Страница 9: ...exterior n cazul lungimilor mari minimum 30 de metri se recomand introducerea unui filtru dV dT pentru a limita v rfurile de tensiune i pentru a proteja durata de via a motorului n special a nf ur ril...

Страница 10: ...invertorul va utiliza a doua valoare de set point a presiunii ca referin pentru func ionarea cu presiune constant atunci c nd este comutat contactul dintre borna C comun i intrarea I 1 Acesta poate fi...

Страница 11: ...ul serial Fiec rui dispozitiv i va fi asociat un num r diferit n caz contrat dac mai multe dispozitive au aceea i adres se creeaz o suprapunere n comunicarea serial cu pierderea datelor transmise Prin...

Страница 12: ...itate de presurizare cu mai multe pompe seta i num rul dispozitivului la care sunt conectate senzorul de presiune i alte eventuale intr ri auxiliare Valoarea trebuie s fie aceea i pentru toate dispozi...

Страница 13: ...atura dispozitivului MASTER valorile setate vor fi partajate i transmise automat celorlalte invertoare conectate REGLAREA FRECVEN EI DE STOP FUNC IA DE SETARE AUTOMAT Dup ce a i adus instala ia n cond...

Страница 14: ...i pute i vedea tensiunea de intrare n invertor i temperaturile ambiant intern i a modulului de putere IGBT Valorile acestor temperaturi contribuie la gestionarea inteligent a puterii care limiteaz val...

Страница 15: ...no regleaz rota ia pompei electrice consulta i i parametrul 3 1 0 5 Delta P stop imediat acest parametru seteaz delta presiunii pozitive fa de set point pentru oprirea imediat a pompei n timpul func i...

Страница 16: ...axim suportat de invertor i de motorul electric GRUPA 2 PARAMETRI FUNC IONARE MULTIPL 2 0 Adres serial n cazul unei singure instal ri cu o singur pomp l sa i valoarea la 1 Dac este realizat un grup de...

Страница 17: ...eaz pe valoarea presiunii m surat de senzor 4 20mA MAN mod manual motorul este pornit de la tastatura Nettuno i viteza poate fi schimbat cu tastele i 0 10V ingresso analogico reglarea are loc pe baza...

Страница 18: ...i sunt accesibili numai serviciului de asisten tehnic Pentru a accesa ace ti parametri contacta i dealerul un centru de asisten tehnic sau produc torul Tabelul urm tor prezint o list de parametri ava...

Страница 19: ...Verifica i condi iile de func ionare a invertorului E5 Temperatur ridicat modul IGBT eroarea apare dac temperatura maxim interioar a modulului IGBT a fost dep it Verifica i condi iile de func ionare a...

Страница 20: ...upape de siguran Valoarea presiunii de protec ie la func ionarea uscat nu este setat corect corecta i valoarea Dispozitivul semnalizeaz frecvent o stare de nalt sau joas tensiune Tensiunea de alimenta...

Страница 21: ...na s fie bine nchis capacul i presetupele s fie bine str nse pentru a evita infiltrarea apei din exterior deconecta i tensiunea i evacua i apa din instala ie c nd sistemul r m ne inactiv pentru o peri...

Страница 22: ...cially trained personnel with the ability to understand the entire contents of this owner s manual For all operations required to be carried out with the cover removed the device must be disconnected...

Страница 23: ...ering Protection against dry running in the event of water shortage during intake Automatic reset in the event of dry running with autonomous clearing of error condition Efficient leakage monitoring t...

Страница 24: ...mmersion in the event of flooding The device must never be installed in confined spaces that can reduce ventilation and therefore cooling of the inverter WALL MOUNTING Nettuno can be mounted on a wall...

Страница 25: ...e that the bracket is securely fitted on the pipe and cannot 4 bolts supplied See fig 6 for selection of the holes rotate 3 Pre assemble the fixing screws on the rear side of 4 Insert Nettuno onto the...

Страница 26: ...ime of pump shutdown In the case of multiple installations it is recommended to install a valve on suction for each pump CAUTION when the pump stops the conduits are still pressured so a valve must be...

Страница 27: ...ly qualified personnel can replace it this is to prevent risks to things and people Fit the electric wires into the relative wire clamps making sure the correct assembly order is maintained for all th...

Страница 28: ...equipped with the electrical protection required Always install upline of the inverter a device that ensures omnipolar disconnection from the mains with a contact opening gap of at least 3 mm Before...

Страница 29: ...le length over 30 metres is used it is recommended to insert a dV dT filter to limit peak current voltage and for motor especially windings longevity Also observe the installation limits as declared b...

Страница 30: ...function is activated via the menu the inverter uses the second pressure set point value as reference for operation at constant pressure when the contact is switched between terminal C common and inpu...

Страница 31: ...vidual number to identify their address in the serial bus Each device must be assigned a different number otherwise if several devices have the same address the serial communication will overlap with...

Страница 32: ...ump leave this value at 1 If a pressurisation unit with multiple pumps is installed set the number of the device to which the pressure sensor and any other auxiliary inputs are connected The value mus...

Страница 33: ...s will be shared and transmitted automatically to the other connected inverters REGULATION OF STOP FREQUENCY AUTOSET FUNCTION After setting up the system for normal conditions of use pump fully primed...

Страница 34: ...inverter input and the internal ambient and IGBT power module temperatures The values of these temperatures contribute to the intelligent power management which limits the value of the maximum frequen...

Страница 35: ...3 1 0 5 Immediate stop Delta P this parameter sets the positive pressure delta compared to the set point for immediate shutdown of the pump During normal operation when the valves close the pump stops...

Страница 36: ...ric motor GROUP 2 MULTIPLE OPERATION PARAMETERS 2 0 Serial address in the case of single installations with a single pump leave this value at 1 If a pressurisation unit with multiple pumps is installe...

Страница 37: ...f the pressure read by the sensor 4 20mA MAN manual the motor is started up via the keypad of Nettuno and the speed can be adjusted using the keys and 0 10V analogue input regulation is based on the s...

Страница 38: ...PARAMETERS The advanced parameters are accessible only to the technical assistance service For access to these parameters it is necessary to contact the re seller a technical assistance centre or the...

Страница 39: ...or appears if the maximum internal ambient temperature of the inverter is exceeded Check the conditions of operation of the inverter E5 IGBT module over temperature the error appears if the maximum te...

Страница 40: ...low increase The expansion tank does not have the correct pre load value check The device often signals dry running The pump intake pipe drains when the system is not used for some time thereby preve...

Страница 41: ...environments reduce the frequency to 6 months if the pump is equipped with intake filters carry out regular checks to ensure they are clean always ensure that the cover is closed properly and the cabl...

Страница 42: ...___________________________________ _____________________________________________ _____________________________________________ _____________________________________________ __________________________...

Страница 43: ...Italtecnica srl V le Europa 31 35020 Tribano PD Italy Tel 39 049 9585388 Fax 39 049 5342439 www italtecnica com italtecnica italtecnica com...

Отзывы: