RO
EN
27
ELECTRICAL CONNECTION:
CAUTION:
- all wiring up must be carried out by specially trained personnel
- an incorrect motor connection could result in damage to the device or the pump motor.
- failure to comply with what is stated in this paragraph may cause serious damage to things and/or serious injuries to people, and
the manufacturer declines all responsibility.
- if the power supply cable or the cable between Nettuno and the electric pump is damaged, only the manufacturer of the device,
its appointee or equally qualified personnel can replace it; this is to prevent risks to things and people.
Fit the electric wires into the relative wire clamps, making sure the correct assembly order is maintained for all the components. Secure
the threaded nuts tightly enough to prevent the wires being pulled or turned from the outside.
Use cable clamps in metal for connection of the power line and those in plastic for connection of any I/O (auxiliary inputs and outputs).
The metal plates located in the vicinity of the cable clamps can be used
to connect the shielding of the cables and thus ensure correct continuity
of the shielding itself with the heat sink.
POWER INPUT
MOTOR
OUTPUT
AUXILIARY
INPUTS/OUTPUTS
SHIELDING
CONNECTION