iSMA-B-LP Room Panel/Modbus
version 1.3
www.gc5.pl
Page 90 / 121
12.1.5
Light Submenu
Modbus
Address
Dec
Address
Hex
Address
Register Name
Access
Description
40075
74
0x4A
LIGHTNUMERIC1
PRESENT_VALUE
Read &
Write
Memory
Present value of the parameter
40807
806
0x326
LIGHT_MENU_ACTIVE_POINTS
Read &
Write
Memory
Number of active parameters in submenu
40810
809
0x329
LIGHTNUMERIC1
NAME (32
–
bits)
Read &
Write
Memory
Displaying user-defined parameter name.
40812
811
0x32B
LIGHTNUMERIC1
STEP
Read &
Write
Memory
STEP during parameter value changing.
The default value is 0
40813
812
0x32C
LIGHTNUMERIC1
LOW_LIMIT
Read &
Write
Memory
Minimal value of the parameter.
The default value is 0
40814
813
0x32D
LIGHTNUMERIC1
HIGH_LIMIT
Read &
Write
Memory
Maximal value of the parameter.
The default value is 0
40815
814
0x32E
LIGHTNUMERIC1
PRIORITY
Read &
Write
Memory
Priority of the parameter for sequence of display in
Submenu
40816
815
0x32F
LIGHTNUMERIC1
CONFIGURATION
Read &
Write
Memory
Bit
Name
0
1
0 Active
Not active(def) Active(def)
2
FirstPointActive Not
decimal(def)
Decimal(def)
3
SecondPointActive Not
decimal(def)
Decimal(def)
4
ThirdPointActive Not
decimal(def)
Decimal(def)
6
C unit active
not_visible(def) visible
7
F unit active
not_visible(def) visible
8
Pa unit active
not_visible(def) visible
9
Lx unit active
not_visible(def) visible
10 ppm unit active
not_visible(def) visible
11 m3/h unit active not_visible(def) visible
12 %Rh unit active
not_visible(def) visible
13 l/s unit active
not_visible(def) visible
14 % unit active
not_visible(def) visible
15 h unit active
not_visible(def) visible
40076
75
0x4B
LIGHTNUMERIC2
Read &
Present value of the parameter