iSMA-B-LP Room Panel/Modbus
version 1.3
www.gc5.pl
Page 60 / 121
11.3
Submenu MenuActivePoints registers
For each Submenu there is a special register which indicates if there is any active
parameters inside the particular submenu. If the value of Menu Active Points register is
higher than 0, it means that there is at least one active parameter in Submenu and icon
assigned to that submenu is displayed.
Menu Active Points register reads values from all XConfiguration Active bits inside a
particular Submenu. If one of Active bit is
“true”
, Register Submenu Active points becomes
positive.
11.4
Submenu Boolean All Present Value registers (40107 - 40113)
For each submenu there is a special register which contains all Boolean present values
inside a particular submenu.
Setting true value for single bit sets true value for assigned Boolean Point according to the
Table below. By default all bits of the register are
“false”
.
Bit Name
0
1
0
Boolean1PresentValue Not active(def) Active
1
Boolean2PresentValue Not active(def) Active
…
…
…
…
…
…
…
…
6
Boolean7PresentValue Not active(def) Active
7
Boolean8PresentValue Not active(def) Active