iSMA-B-LP Room Panel/Modbus
version 1.3
www.gc5.pl
Page 29 / 121
5
Sensors Configuration
There are 3 different sensors which can be built-in in the Room Panel (depending on which
Room Panel version is chosen - see
Table 3
)
:
•
Temperature sensor
•
Humidity sensor
•
CO
2
sensor
Actual values from all in-built sensors can be displayed in the Main Menu in a specific order
(see section
LCD Display
).
Actual sensor values are displayed on 8-segment display block in the LCD display, at the
same time.
14-segment display block shows the name of the parameter actual value of which is
displayed on 8-segment display block. Every numeric value is displayed with assigned unit.
Figure 16 Actual temperature sensor value displayed on 8-segment displays block
and the temperature name displayed on 14 -segment displays block
5.1
Temperature Sensor
All Room Panel versions have in-built temperature sensor. Default temperature unit is
o
C and
it is displayed together with temperature sensor value (if active).
5.1.1
TEMPERATURE_SENSOR_ACTUAL_VALUE (30301)
Register stores actual value from the temperature sensor (including Temperature Sensor
Offset) multiplied by 10. In the Main Menu the temperature sensor value is displayed directly
(without multiplying). Actual register value is calculated according to the equation:
Actual temperature (register value) = (Actual Sensor Temperature +Temperature Sensor
Offset)*10