Group access: Status1 Voltage limit
(Read-write access)
Byte
DATA_ID
Controller:
Bit
7
6
5
4
3
2
1
0
Check exceeding voltage limit per channel
Designation
DATA
_DIR
Data
1
1
1
0
0
0
1
0
0
Description
read
⇓
Response module (DLC = 3)
Byte
DATA_ID
DATA_1
DATA_0
Bit
7
6
5
4
3
2
1
0
7
...
0
7
...
0
Designation
DATA
_DIR
Data
0
1
1
0
0
0
1
0
0 x15
...
x8 x7
...
x0
Description
write
x0
⇒
Status for Channel 0
x
n
= 0
⇒
Channel ok
:
x7
⇒
Status for Channel 7
x
n
= 1
⇒
Voltage limit has
been exceeded
If an external over voltage occurs at the channel output (i.e. Output voltage > Set voltage) then the channel will
be switched off and the according bit will be set. Only after the read of ‘Status 1 voltage limit’ this bit will be
cancelled.
Group access: Status2 Hardware current limit
(Read-write access)
Byte
DATA_ID
Controller (DLC = 1):
Bit
7
6
5
4
3
2
1
0
Check exceeding hardware current limit per channel
Designation
DATA
_DIR
Data
1
1
1
0
0
1
0
0
0
Description
read
⇓
Response module (DLC = 3)
Byte
DATA_ID
DATA_1
DATA_0
Bit
7
6
5
4
3
2
1
0
7
...
0
7
...
0
Designation
DATA
_DIR
Data
0
1
1
0
0
1
0
0
0 x15
...
x8 x7
...
x0
Description
write
x0
⇒
Status for Channel 0
x
n
= 0
⇒
Channel ok
:
x7
⇒
Status for Channel 7
x
n
= 1
⇒
Hardware
current limit has been
exceeded.
The module responds to the exceeding of the hardware current limit which has been set in the channel in
dependence to the according KILL-enable bit (see also Group access ‘KILL-enable’) as follows:
KILL-enable = 1: Voltage will be switched off permanently without ramp, green LED on front panel is off.
KILL-enable = 0:
Voltage will be switched off without ramp, green LED on front panel is off. If the output
voltage arrives at 0 V ramping to set voltage will be started automatically again.
The green LED flashes on again only after the Group access ‘Status2 Current limit’ has
been read.