Proceed as follows for this purpose:
1. Select the device in the ETS.
2. Display the device properties in the sidebar on
the ETS as shown in Figure 4.
Figure 4: Device properties dialogue of the
ETS.
3. Select the
IP
tab as per Figure 5. Then select ei-
ther
Obtain an IP address automatically (default)
The address data are automatically obtained
from a DHCP server on the data network.
or
Use the following address
and enter the data manually.
You can usually obtain the permissible IP ad-
dress range and the subnet mask and standard
gateway from the router configuration interface.
If the
Obtain an IP address automatically
setting is
used, a DHCP server must issue the ise smart connect
KNX Hue a valid IP address.
If a DHCP server is not available for this setting, the
device starts up after a waiting time with an AutoIP ad-
dress (address range from 169.254.1.0 to
169.254.254.255).
As soon as a DHCP server is available, the device is
automatically assigned a new IP address.