24
DESCRIPTION
DISPLAYED
Code
ALS10
FULL MEMORY
The newly recorded item
cancels the last one on the list
Recording memory full
Slave-CPU
NO
ALS11
Low voltage
Electronic card block
Card power supply
voltage less than 33%
Slave-CPU
YES
ALM00
Loss of data
Loading of default data
Master
NO
ALM01
Low voltage
Card power supply
voltage less than
Visual alarm only
Master
NO
ALS13
Slave serial faulty
Block of cell card and
automatic reset
Failure in serial port of
the card
Slave-CPU
YES
ALS14
Front serial faulty
Block of cell card and
automatic reset
Failure in serial port of
the card
Slave-CPU
YES
ALS15
Defrosting timeout
The alarm is only recorded
in the record of alarms
The defrost cycle has
ended due to elapsed
safety time
Slave-CPU
YES
ALS12
Thawing
The temperature of the
cell has risen above the
temperature set in
parameter 2-1 after the
time set in parameter 2-2.
In addition, the cell
temperature and defrost
probes are faulty
Slave-CPU
YES
CAUSE
EFFECT
CARD
CYCLE
STOP
ALM02
Power outage
Automatic restart when
power comes back on
Master
NO
ALM03
Master serial/external
Visual alarm only
Master
NO
ALM04
Low voltage
Card power supply
voltage less than 33%
Electronic card block
Master
YES
ALM05
Power outage
Master
YES
ALM06
Thermal 1
Circuit breaker
compressor 1, open
Master
YES
ALM07
Thermal 2
Circuit breaker
compressor 2, open
Master
YES
ALM08
Thermal 3
Circuit breaker
compressor 3, open
Master
YES
ALM09
Thermal 4
Circuit breaker
compressor 4, open
Master
YES
ALM10
Press. Mech.
Activation of high
pressure switch
Cycle stop and automatic
restart when alarm ceases
Master
YES
ALM11
Master/Slave
serial faulty
Failure of the serial
port for communications
between the cell card and
the condenser card
Block of condenser card
and automatic reset
Master
YES
Содержание C504