10
CELL ELECTRONIC
CARD
CABLE 3x0.5 mm
2
TWISTED
SHIELDED
GND
B
A
CONDENSING UNIT
ELECTRONIC CARD
GND
B
A
Table 5
"Unit communication BUS cable"
MODEL
POWER SUPPLY
POWER INPUT
CABLE SECTION
Voltage (V)
Frequency (Hz)
Poles
Power (kW)
Current (A)
Cabinet CP40
208
2P + PE
1,2
5,8
3G11AWG
C504A
208
60
60
2P + PE
1,2
5,7
3G11AWG
C504M
208
2P + PE
1,2
6,0
3G11AWG
C504W
208
2P + PE
1,1
5,4
3G11AWG
C504S.S.
208
2P + PE
1,2
6,0
3G11AWG
60
60
60
NOTE: cable sized for a length of 25m with industrial voltage drop ∆V% ≤ 1%
A: Air - M: Mixed Air/Water- W: Well water - S.S.: Super Silenced
BUS cable for communication between condensing unit and cells
Twisted and shielded cable 3x0.5mm
2
maximum length
100m.
Connect the cable to the terminals of the electronic
cards as shown in the block diagram and in the electri-
cal diagrams. Comply with the codes on the terminal
block. The sequence of connection of the units does
not make any difference. Start with the BUS of the
Master card (condensing unit).
Connect the shield of the BUS cable to earth only in the
electrical panel of the condensing unit.
ATTENTION! The shield must be connected to earth only in the condensing unit.
If several cells are to be connected with the bus, the shield of the incoming cable must be spliced with the shield of
the outgoing cable. In the cell where the bus ends, the shield must be isolated.
The manufacturer declines any responsibility
or guarantee obligations if damage occurs to the
unit, persons or things due to installation that is
incorrect and/or does not respect the laws in force.