U-MATCH AIR CONDITIONERS MAINTENANCE
91
Trouble
Code
Trouble Name
Origin of
Trouble Signal
Control Description
fault is displayed and the indoor fan is running normally. The
fault display disappears when the fault is removed.
F1
Failure of Evaporator
Temp. Sensor
Indoor evaporator
thermal bulb
Open-circuit or short-circuit of evaporator thermal bulb is
detected for continuous 5 seconds, under refrigeration and
dehumidification mode, the system will be shut off; and under
heating mode, all loads except for the four way valve are shut
off. The indicator is twinkling or fault code F1 is displayed. The
system can restore by itself and display fault elimination after the
fault is removed. Under air supply mode, only the fault is
displayed and the indoor unit is running normally. The fault
display disappears when the fault is removed.
F2
Failure of Condenser
Temp. Sensor
Outdoor condenser
thermal bulb
Open-circuit or short-circuit of condenser thermal bulb is
detected for continuous 5 seconds, under refrigeration and
dehumidification mode, the system will be shut off; and under
heating mode, all loads except for the four way valve are shut
off. The indicator is twinkling or fault code F2 is displayed. The
system can restore by itself and display fault elimination after the
fault is removed. Under air supply mode, only the fault is
displayed and the indoor unit is running normally. The fault
display disappears when the fault is removed.
For other types of refrigeration machines except for air duct
machine, condenser thermal bulb is not detected.
F3
Failure of Outdoor
Ambient Sensor
Outdoor environment
thermal bulb
Open-circuit or short-circuit of outdoor environment thermal
bulb is detected for continuous 5 seconds, under refrigeration and
dehumidification mode, the system will be shut off; and under
heating mode, all loads except for the four way valve are shut
off. The indicator is twinkling or fault code F3 is displayed. The
system can restore by itself and display fault elimination after the
fault is removed. Under air supply mode, only the fault is
displayed and the indoor unit is running normally. The fault
display disappears when the fault is removed.
F4
Failure of Exhaust
Temp. Sensor
Discharge thermal
bulb
After the compressor is started, open-circuit of discharge thermal
bulb is detected for continuous 5 seconds. Under refrigeration
and dehumidification mode, all loads will be shut off. Under
heating mode, all loads except for the four way valve are shut
off. The indicator is twinkling or fault code F4 is displayed. And
the buzzer gives out an alarm. After the fault is removed, the
system will restore by itself and clear the fault code.
Содержание u-match on/off
Страница 1: ......
Страница 4: ...INVENTOR COMMERCIAL AIR CONDITION U MATCH AIR CONDITIONERS 1 PRODUCT...
Страница 24: ...U MATCH AIR CONDITIONERS PRODUCT 21 5 PIPING DIAGRAM...
Страница 25: ...INVENTOR COMMERCIAL AIR CONDITION U MATCH AIR CONDITIONERS 22 CONTROL...
Страница 26: ...U MATCH AIR CONDITIONERS CONTROL 23 CONTROL 1 OPERATION FLOWCHART 1 1 Cooling Dry Operation...
Страница 27: ...U MATCH AIR CONDITIONERS CONTROL 24 1 2 Heating Operation...
Страница 45: ...U MATCH AIR CONDITIONERS CONTROL 42 5 2 4 Dimensions...
Страница 48: ...INVENTOR COMMERCIAL AIR CONDITION U MATCH AIR CONDITIONERS 45 INSTALLATION...
Страница 91: ...INVENTOR COMMERCIAL AIR CONDITION U MATCH AIR CONDITIONERS 88 MAINTENANCE...
Страница 97: ...U MATCH AIR CONDITIONERS MAINTENANCE 94 Malfunction display E1 Compressor High Pressure Protection...
Страница 98: ...U MATCH AIR CONDITIONERS MAINTENANCE 95 Malfunction display E3 Compressor Low Pressure Protection...
Страница 101: ...U MATCH AIR CONDITIONERS MAINTENANCE 98 Malfunction display E6 Communications Failure...
Страница 107: ...U MATCH AIR CONDITIONERS MAINTENANCE 104 2 ULS 12 WITH FUNCTION OF LOW TEMP COOLING WITHOUT FUNCTION OF LOW TEMP COOLING...
Страница 108: ...U MATCH AIR CONDITIONERS MAINTENANCE 105 3 ULS 18 WITH FUNCTION OF LOW TEMP COOLING WITHOUT FUNCTION OF LOW TEMP COOLING...
Страница 109: ...U MATCH AIR CONDITIONERS MAINTENANCE 106 4 ULS 24 WITH FUNCTION OF LOW TEMP COOLING WITHOUT FUNCTION OF LOW TEMP COOLING...
Страница 111: ...U MATCH AIR CONDITIONERS MAINTENANCE 108 6 ULT36 WITH FUNCTION OF LOW TEMP COOLING WITHOUT FUNCTION OF LOW TEMP COOLING...
Страница 112: ...U MATCH AIR CONDITIONERS MAINTENANCE 109 7 ULT 45 WITH FUNCTION OF LOW TEMP COOLING WITHOUT FUNCTION OF LOW TEMP COOLING...
Страница 115: ...U MATCH AIR CONDITIONERS MAINTENANCE 112...
Страница 163: ......