U-MATCH AIR CONDITIONERS INSTALLATION
78
connecting pipe is needed to lengthen, appropriate amount of refrigerant should be added.
How much refrigerant should be added for every meter extension refers to the following table.
Allowable maximum pipe length is 30m.
If height difference between indoor unit and outdoor unit exceeds 10m in installation of air
conditioner, an oil return bend must be mounted at an interval of 6m.
If heights of indoor unit and outdoor unit are different, pipes should be laid out with reference
to Figure 3-2-1.
Refrigerant pipe (thin)
- - - - - - Air pipe (large)
Figure 3-2-1
3.3 Specification of Connection Pipe
Model
External Diameter
Maximum
Length
of Connection
Pipe
Maximum Difference
in Height between
Outdoor and Indoor
Unit
Additional
Charge
of
Refrigerant
Gas Pipe
Liquid Pipe
(m) (m)
(g/m)
ULS-09
3/8
ʾ
1/4
ʾ
20 15
15
ULS-12
1/2
ʾ
ULS-18
ULS-24
5/8
ʾ
3/8
ʾ
30 15
60
ULS-36
3/4
ʾ
1/2
ʾ
50 30
120
Refrigerant pipes
Air pipe
Outdoor unit
Oil loop of air pipe
Oil loop of air pipe
An oil loop is arranged at an
interval of 4-6m.
indoor unit
Содержание u-match on/off
Страница 1: ......
Страница 4: ...INVENTOR COMMERCIAL AIR CONDITION U MATCH AIR CONDITIONERS 1 PRODUCT...
Страница 24: ...U MATCH AIR CONDITIONERS PRODUCT 21 5 PIPING DIAGRAM...
Страница 25: ...INVENTOR COMMERCIAL AIR CONDITION U MATCH AIR CONDITIONERS 22 CONTROL...
Страница 26: ...U MATCH AIR CONDITIONERS CONTROL 23 CONTROL 1 OPERATION FLOWCHART 1 1 Cooling Dry Operation...
Страница 27: ...U MATCH AIR CONDITIONERS CONTROL 24 1 2 Heating Operation...
Страница 45: ...U MATCH AIR CONDITIONERS CONTROL 42 5 2 4 Dimensions...
Страница 48: ...INVENTOR COMMERCIAL AIR CONDITION U MATCH AIR CONDITIONERS 45 INSTALLATION...
Страница 91: ...INVENTOR COMMERCIAL AIR CONDITION U MATCH AIR CONDITIONERS 88 MAINTENANCE...
Страница 97: ...U MATCH AIR CONDITIONERS MAINTENANCE 94 Malfunction display E1 Compressor High Pressure Protection...
Страница 98: ...U MATCH AIR CONDITIONERS MAINTENANCE 95 Malfunction display E3 Compressor Low Pressure Protection...
Страница 101: ...U MATCH AIR CONDITIONERS MAINTENANCE 98 Malfunction display E6 Communications Failure...
Страница 107: ...U MATCH AIR CONDITIONERS MAINTENANCE 104 2 ULS 12 WITH FUNCTION OF LOW TEMP COOLING WITHOUT FUNCTION OF LOW TEMP COOLING...
Страница 108: ...U MATCH AIR CONDITIONERS MAINTENANCE 105 3 ULS 18 WITH FUNCTION OF LOW TEMP COOLING WITHOUT FUNCTION OF LOW TEMP COOLING...
Страница 109: ...U MATCH AIR CONDITIONERS MAINTENANCE 106 4 ULS 24 WITH FUNCTION OF LOW TEMP COOLING WITHOUT FUNCTION OF LOW TEMP COOLING...
Страница 111: ...U MATCH AIR CONDITIONERS MAINTENANCE 108 6 ULT36 WITH FUNCTION OF LOW TEMP COOLING WITHOUT FUNCTION OF LOW TEMP COOLING...
Страница 112: ...U MATCH AIR CONDITIONERS MAINTENANCE 109 7 ULT 45 WITH FUNCTION OF LOW TEMP COOLING WITHOUT FUNCTION OF LOW TEMP COOLING...
Страница 115: ...U MATCH AIR CONDITIONERS MAINTENANCE 112...
Страница 163: ......