35
range
Default
value
- 00:00
Comment
- This parameter sets the point on the 24-hours time scale which
is then used as the reference for the moments when
measurements and data transmissions begin
6.1.5.2.2. Measure timer (T1)
The
Measure timer
is responsible for periodic activation of the module in order to
make the signal measurements, to compute the signal increments, to check the
alarm levels and then to process the rules.
6.1.5.2.2.1. Period
Function
- A repetition period for the
Measure timer
activation
Data type
- Selection
list
Variation
range
-
5 minutes
,
15 minutes
,
30 minutes
,
1 hour
,
3 hours
,
6
hours
,
8 hours
,
12 hours
,
24 hours
Default
value
-
24 hours
Comment
- This parameter defines how frequently the module is
activated to make the measurement, write its result into the
data logger, evaluate alarms and process the rules. The
repetition period begins in the moment defined by the
Start
parameter value
6.1.5.2.3. Transmission timer (T2)
The
Transmission timer
was originally designated to initiate a transmission of the
data logger content (if enabled), but its cycle can be also used in other transmission
tasks.
6.1.5.2.3.1. Period
Function
- A repetition period for the
Transmission timer
activation
Data type
- Selection
list
Variation
range
-
5 minutes
,
15 minutes
,
30 minutes
,
1 hour
,
3 hours
,
6 hours
,
8 hours
,
12 hours
,
24 hours
Default
value
-
24 hours
Comment
- This parameter defines how frequently the module is activated
to send the data logger content. The repetition period begins
in the moment defined by the
Start
parameter value
ATTENTION!!!
Due to the operational purposes the Transmission timer period
should not be shorter than the period set for the Measure timer.