24
6.1.2.8. Low battery voltage alarm
Function
- Sets alarm level for the module supply voltage
Data type
- Number
Variation
range
- 0.01…100.00
Default
value
-
Standard
Associated
flag
- Bat_Low
Comment
- Setting the flag on low battery voltage alarm is important, because
the battery is the only one available power source for the module.
Normally it is hard to precisely define the remaining battery
capacity and its usability time, so this flag may be useful
6.1.3. The GPRS group
The
GPRS
group contains GPRS login and transmission parameters. Parameters
assigned to this group are either obligatory or optional or used for the transmission
optimization.
6.1.3.1. APN name
Function
- Name of the APN used in GPRS transmission
Data type
- Text
Variation
range
- Letters, digits and special characters - 32 characters maximum
Default
value
- Empty
Comment
- Lack of the APN disables login to the GPRS
6.1.3.2. APN user name
Function
- Name of the user allowed for access to the APN used in GPRS
transmission
Data type
- Text
Variation
range
- Letters, digits and special characters - 32 characters maximum
Default
value
- Empty
Comment
- Optional parameter, entered only if required by the GSM
network operator
6.1.3.3. APN login password
Function
- Login password for access to the APN used in GPRS transmission
Data type
- Text
Variation
range
- Letters, digits and special characters - 32 characters maximum
Default
value
- Empty
Comment
- Optional parameter, entered only if required by the GSM
network operator