13
PREPARING FOR INSTALLATION
Ventilation device iV14-MaxAir
•
Installation and operating instructions
3
Preparing for installation
3.1
Installation position
• The installation location can be derived from the position suggested by the ventilation planning.
The exact positioning of the individual devices and control units must be checked on site and,
if necessary, adjusted.
Consult the responsible planner about this.
For optimum function,
it is recommended that the ventilation device is installed at the appropriate point in the upper
wall area (e.g. 1.80 m from the upper edge of the finished floor (OKFFB)).
• Do not place the ventilation device near radiators, indoor air thermostats, sensitive furniture
or above pictures.
• Do not install the device in places where direct contact with water spray is possible. Observe
the specifications of VDE 0100 when choosing the installation location.
• Observe the following
minimum distances of the wall opening for the ventilation device
:
1 between two ventilation devices (pair of devices) operating in push-pull mode in a room
to prevent an airflow short circuit:
A
B
C
1,2 m
1,0 m
1,0 m
1,4 m
y
1,2 m – 0,75 y
1,2 m
1,0 m
1,0 m
1,4 m
y
1,2 m – 0,75 y
1,2 m
1,0 m
1,0 m
1,4 m
y
1,2 m – 0,75 y
Installation horizontal or vertical
(on the same wall):
Installation with height offset:
Installation over corner:
1.0 m
1.0 m
1.4 m
1.2 m
1.2 m – 0.75 y
2 to adjoining building components on the exterior wall (note insulation thickness / roller shutters):
Flex weather protection hood:
450 mm from borehole centre/centre axis
3 to adjoining components on the interior wall:
250 mm from borehole centre/centre axis
4 to frontally adjacent components:
300 mm for cleaning work