GS62 Air Extraction System •
Installation and Operating Instructions 09/2013
FUNCTIONAL ELEMENTS/INSTALLATION
4 FUNCTIONAL ELEMENTS / INTERFACES
4.1 GS61 PSU
Power supply (AC 230V, 50 Hz)
Fan connector (-)
Fan connector (+) or functional module (+)
Figure 3: Connectors on GS61 PSU
5 INSTALLATION
5.1 Installation preparation
Dimensions
Name
Comprising:
Length (mm)
LxW / diameter (mm)
Hole for
Wall thickness
Ø 115
telescopic tube -
(with insulation, interior/exterior plaster)
Telescopic tube Sleeve
300
Ø 107
Tube
300
Ø 103
Extension
Identical in design to combination Wall mounting sleeve / telescopic tube
Flat duct
-
500
209x65
-
1000
Opening for
-
87
Ø ≥ 75
wall mounting box
Wall mounting box -
87
Ø 73
Note
- Keep a minimum distance of 100mm from the center of the wall mounting sleeve to
walls, to components in the interior area as well as to fixtures and fittings.
Wall holes and cable laying
Danger
- Make the opening for the wall mounting box outside protective areas 0 to 2 of the
room. This will ensure that no moisture can penetrate in.
1.
Make two holes in the masonry - one (Ø75) for the wall mounting box and one (Ø115) for the telescopic
tube. Ensure that the hole for the wall mounting sleeve of the GS62 is at an angle of 1-2° to the outside
wall so that condensation is drained away reliably.
2.
Lay the 2-wire connecting lead (red/white) for the wall mounting box in the cable duct such that the cable
ends project out of each wall opening by at least 150mm. This ensures that the PSU and switch can be
connected with terminal blocks.
Note
- The dimensional drawings for all holes are in Section Dimensional drawings.