Horizontal Termination

 Any horizontal termination must fall within the shaded 

portion of the vent window graph illustrated in figs. 9 

or 11.  For Snorkel Terminations, see below.

 Any horizontal termination except a snorkel termina-

tion, must include:

  1)   Minimum rise of 2 ft.

 

2)  Minimum horizontal run of 12 in. when vertical  

 

run is less than 8 ft.

 

3)  Maximum rise of 35 ft.

 

4)  Maximum horizontal run of 27 ft.

 

5)  No more than four 45° or two 90° Elbows

 Follow all termination clearance guidelines as specified 

in fig. 19.

 

The horizontal termination cap must maintain a 3" 

clearance to any overhead combustible projections  

 

2 1/2" or less. It must also maintain 12" clearance from 

projections exceeding 2 1/2".  See fig. 20.

 Wall Cut-out Opening: A minimum 10" X 10" (250 mm x 

250 mm) square hole is required for proper pipe clear-

ances through a combustible wall. 

Use a listed wall 

thimble for the wall penetration.

 

DO NOT FILL AIR SPACE WITH ANY TYPE OF INSULA

-

TION.

 

Any horizontal run of vent must have a 1/4" rise for ev

-

ery foot of run toward the termination cap. NEVER AL-

LOW THE VENTING TO RUN DOWNWARD FROM STOVE 

TO TERMINATION; 

DOWNWARD VENT RUNS TRAP HEAT 

AND CAUSE HIGH TEMPERATURES TO DEVELOP WITHIN 

THE VENT THAT COULD START A FIRE.

 

Install a Vinyl Siding Standoff between the vent termi-

nation and an exterior wall covered by vinyl siding ma-

terial to prevent potential heat damage to the siding.

 

Do not recess the termination cap into a wall or siding.

Figure 16.  

• Minimum vent for horizontal termination.
• 14” Maximum horizontal run directly off rear of stove 

with 14” Snorkel termination.

Figure 17.  Maximum Horizontal and Vertical Run with 36” 

Snorkel Termination.

Max. 

 

6 ft.

183 cm

36 in.

Snorkel 

(915 mm)

Figure 18.  Corner Installation with 14” Snorkel Termination.

Snorkel  Terminations

 

THE AIR INLET RESTRICTOR MUST BE SET FULLY OPEN 

FOR ANY SNORKEL TERMINATION.

 See Fig. 6, pg. 9.

 

With a 14” Snorkel:

The horizontal run made directly off the rear of the 

stove into a 14” snorkel cap should include no more 

than a single 12” straight section as shown in fig. 17. 

 

One 45° Elbow may be used for a corner installation as 

shown in fig. 18.

 

With a 36” Snorkel:

The maximum horizontal run may be no more than  

6 ft. (182 cm.)

 

12 in. 

Straight Pipe

Max. 14”

355 mm

Wall Thimble 

and Trim Collar

45° Elbow

See Note F 

Fig. 20

14”

355 mm 

Max.

12 in.

(305 mm)

12” 

Vent 

Pipe or 

less

57”

(1448 mm)

24 in.

Snorkel

(305 mm)

25 1/2 in.

Snorkel

(648 mm)

Содержание Jotul GF 400 DV Sebago

Страница 1: ...r future reference QUEFAIRESIVOUSSENTEZUNEODEURDEGAZ Ne pas tenter d allumer l appareil Ne touchez aucum interrupteur Ne pas vous servir des t l phones se trouvant dans le b timent o vous trouvez Appe...

Страница 2: ...used Installation shall be in strict compliance with the manufacturer s instructions A copy of the installation instructions must remain with the appliance or equipment at the completion of the instal...

Страница 3: ...634 Test Standards This appliance complies with National Safety standards and is tested and listed by Intertek Testing Services of Middleton Wisconsin to ANSI Z21 88 2009 ANSI Z21 88 CSA 2 33 2009 CAN...

Страница 4: ...m input Propane 32 000 BTU hr maximum input 16 000 BTU hr minimum input Inlet Pressure MIN MAX Natural Gas 5 0 WC 1 24 kPa 7 0 WC 1 74 kPa Propane 12 0 WC 2 99 kPa 14 9 WC 3 71 kPa Manifold Pressure M...

Страница 5: ...tion that is not specifi cally addressed in this manual defaults to local code In the absence of local codes the installation require ments must comply with the current National codes In the U S these...

Страница 6: ...adultes doivent tre avertis des dangers des temp ratures de surface lev es et devraient rester l cart pour viter les br lures ou l inflammation des v tements Young children should be supervised while...

Страница 7: ...Alcove dimensions result from test configurations not stove clearance specifications Minimum Clearances from the Vent Pipe to Combustibles Horizontal Run Off the top of the pipe 2 51 mm Off the sides...

Страница 8: ...ig 7 3 Tighten the lock nut and replace the Top Plate Venting Requirements This appliance may be installed with a vertical or horizon tal termination and must conform to the configuration requirements...

Страница 9: ...run at three feet intervals to avoid excessive stress on the offsets Elbows Four 45 or two 90 elbows may be used Do not include the 45 elbow attached to the stove When ever possible use 45 elbows inst...

Страница 10: ...cled letter designations in the vent diagram correspond to the Exhaust Restrictor Setting on the stove First determine which vent termination zone is appropriate for your installation and fuel type th...

Страница 11: ...TICAL TEMINATIONS ONLY SET STOVE EXHAUST RESTRICTOR TO THE POSITION THAT COR RESPONDS TO THE VENT TERMINATION AREA IN THE DIAGRAM ABOVE OPEN AIR INLET RESTRICTOR FOR TERMINATIONS 5 FT AND UNDER SEE FI...

Страница 12: ...the unit and the termination cap A METAL BLOCK OFF PLATE MUST BE CONSTRUCTED AND INSTALLED ABOVE THE UNIT PRIOR TO THE END OF THE INTAKE FLEX AND MUST COMPLETELY SEAL THE CHIMNEY FLUE FROM THE ROOM Co...

Страница 13: ...UL 103 or ULC S 629 listed and have a minimum INSIDE diameter of 6 inch es 150 mm Prefabricated chimneys must be listed for the specific Chimney Conversion Kit you choose Figure 15 Vent System through...

Страница 14: ...NWARD FROM STOVE TO TERMINATION DOWNWARD VENT RUNS TRAP HEAT AND CAUSE HIGH TEMPERATURES TO DEVELOP WITHIN THE VENT THAT COULD START A FIRE Install a Vinyl Siding Standoff between the vent termi natio...

Страница 15: ...ly within 3 feet 90 cm horizontally from the center line of the regulator I Clearance to service regulator vent outlet 3 feet 91 cm minimum J Clearance to nonmechanical air supply inlet to building or...

Страница 16: ...HIBITED BY LOCAL CODES THIS APPLIANCE IS ONLY FOR USE WITH THE TYPE OF GAS THAT IS INDICATED ON THE STOVE S RATING PLATE A GAS CONVERSION KIT IS PROVIDED WITH THE GF 400 SEBAGO DIRECT VENT GAS STOVE C...

Страница 17: ...low replacement of the Burner Plate 10 Replace the Burner Plate Engage the Air Inlet Tube with the Air Shutter and burner orifice Properly seated the burner plate will be engaged at its front corners...

Страница 18: ...d and tighten screws securely 16 Install the identification labels to the stove so that they can be seen by any person that may be servicing the stove Label A apply to back of stove Label B apply to s...

Страница 19: ...ons on the inside back cover of this manual or on the stove s rating plate 3 Brush or spray all joints and connections with the soapy water solution 4 If bubbles appear at any connection or seam or a...

Страница 20: ...to burn natural gas with the air shutter set half open Be aware however that this initial setting may not provide the optimal flame picture in your particular installation No single setting will be ap...

Страница 21: ...Middle Log Figure 37 Install Ember Stones Figure 36 Install Crossover Log PILOT OPENING DO NOT OBSTRUCT The ember stones realistically simulate glow ing coals when the burner is operating These shoul...

Страница 22: ...igure 39 Flame appearance on the high setting after approximately 15 to 20 minutes burning WARNING AIR SHUTTER ADJUSTMENTS SHOULD ONLY BE PER FORMED BY A QUALIFIED PROFESSIONAL SERVICE TECHNICIAN Figu...

Страница 23: ...is vacuum this area frequently Always keep the appliance area clear and free from combustible materials gasoline and other flammable liquids If a vacuum is used during any service on the stove ALWAYS...

Страница 24: ...bled for any reason it should be reassembled and sealed according to the manufac turer s instructions provided at the initial installation Burner and Logset Periodically inspect the Firebox Valve Comp...

Страница 25: ...he Blower Bracket to the stove using the two M6 flange head hex bolts as shown in fig 44 4 Attach the Duct Deflectors using the two 7 x 1 2 screws together with the finger guard mounting screws alread...

Страница 26: ...nually adjusted with the rheostat knob If the burner turns off the blower will be shut off automatically when the stove cools down If automatic blower circulation is not desired place the blower contr...

Страница 27: ...their own against the wall Push them back against the Rear Panel Fig 51 6 Reinstall the Logset See page 21 BE CERTAIN THAT NO EMBERS ARE BLOCKING THE PILOT ASSEMBLY OPENING 7 Replace the Glass Frame...

Страница 28: ...Rev_L 11 16 12 Figure 52 Illustrated Parts Breakdown GF 400 DV Sebago GF 400 DV Sebago Illustrated Parts Breakdown Center mount Valve shown used on models after SN 30000 Side mounted Valve uses same c...

Страница 29: ...mostat 750003 Remote Control 750002 Floor Bracket Kit 750304 Fuel Conversion Kit to Propane 155351 Fuel Conversion Kit to Natural Gas 155352 37 Firebox Assembly 221960 38 Latch Assembly 220091 39 Reli...

Страница 30: ...osts associated with the repair of gas controls plumbing burners log set or sheet metal firebox beyond the warranty period 5 Damage caused by unauthorized modification use or repair 6 Damage to enamel...

Страница 31: ...knob Never use tools If the knob will not push in or turn by hand do not try to repair it Call a qualified technician Force or attempted repair may result in a fire or explosion D Do not use this app...

Страница 32: ...beginning the installation it is important that these instructions be carefully read and understood J tul maintains a policy of continual product development Consequently products may differ in specif...

Отзывы: