10
137750_Rev_L 11.16.12
Figure 9. Coaxial Vent Termination Window / NG
Figure 10 . Colinear Termination / NG
•
ALL VENTING MUST TERMINATE (END) WITHIN ONE OF
THE SHADED AREAS.
• SET STOVE EXHAUST RESTRICTOR TO THE POSITION THAT
CORRESPONDS TO THE VENT TERMINATION AREA IN THE
DIAGRAM ABOVE.
• ALWAYS MAINTAIN THE PROPER CLEARANCES TO COM-
BUSTIBLES.
The circled letter designations in the vent diagram correspond
to the Exhaust Restrictor Setting on the stove. First, determine
which vent termination zone is appropriate for your installation
and fuel type, then adjust the restrictor to the corresponding
position as shown in Figure 7, page 9.
Vent Termination Zones - Natural Gas
Vertical
Termination for
COLINEAR VENT
Horizontal and Vertical
Terminations for COAXIAL VENT
•
VENTING MUST TERMI
-
NATE (END) WITHIN THE
SHADED AREA.
• Adjust the Exhaust Re-
strictor to position B
for
any NG colinear termi-
nation.