Combo Output Module
Product Manual
©2017 INTERRA
67
PM131126001A
5.5.2.2.
Objects
The following object can be used through the fan coil 4 pipes function:
OBJ NAME
FUNCTION
TYPE
FLAG
OutputX
Feedback for Fan Coil
Active
1 bit
CRWT
This object is only visible when the “Feedback Telegram” function is enabled (Normal or Inverted). Via the
group address linked, it indicates the current status of the fan coil (valve output status).
OutputX
Man. Fan Level Value
1 byte
CRWU
This object is only visible when the “Manual Fan Control” function is enabled. Via this object, it is possible
to force the fan speed. When a value is sent via the group address linked, no further data is taken into
account.
OutputX
Heating/Cooling
Change
Over
1 bit
CRWTU
This object is only visible when the “Fan Coil Function” parameter is set to “Change Over Object”. Via this
object it is possible to define the operating mode of the fan coil.
OutputX
Feedback for Fan Level 1
1 bit
CRWTU
This object is only visible when the “Feedback Type” parameter is set to “Fan Levels Individually”. Via the
group address linked, it indicates the current status of the fan speed 1.
OutputX
Feedback for Fan Level 2
1 bit
CRWTU
This object is only visible
when the “Feedback Type” parameter is set to “Fan Levels Individually”. Via the
group address linked, it indicates the current status of the fan speed 2.
OutputX
Feedback for Fan Level 3
1 bit
CRWTU
This object is only visible when the “Feedback Type” parameter is set to “Fan Levels Individually”. Via the
group address linked, it indicates the current status of the fan speed 3.
OutputX
Disabling
1 bit
CRWU
This object is only visible when the
“Disabling Function” is enabled. Via this object the “Disabling” function
can be activated.
OutputX
Return to Automatic Mode
1 bit
CRWTU
This object allows the system to return to operate in automatic mode. When this object takes the value 1,
any fan forced is disabled and the system start to work according to the last command received.
OutputX
Feedback for Active Fan
Level
1 byte
CRWTU
This object is only visible when the “Feedback Type” parameter is set to “Fan Level via value”. Via the group
address linked, it indicates the current status of the fan speed such as 1, 2 or 3.
OutputX
Command
Value
For
Heating
1 byte
CRWU
This object is only visible when the “Fan Coil Function” parameter is set to “Only Heating” or
“Heating/Cooling”. Via this object, command value for heating operation is sent.
OutputX
Command
Value
For
Cooling
1 byte
CRWU
This object is only visible when the “Fan Coil Function” parameter is set to “Only Cooling” or
“Heating/Cooling”. Via this object, command value for heating operation is sent.