Combo Output Module
Product Manual
©2017 INTERRA
46
PM131126001A
5.3.2.
Objects
The following object can be used through the shutter/blind function:
OBJ NAME
FUNCTION
TYPE
FLAG
OutputX
Up / Down
1 bit
CRWT
Via this object up and down telegrams are sent.
OutputX
Scene
1 byte
CRWU
This object is used to recall or store the different scenes previously configured.
OutputX
Slat Angle / Stop
1 byte
CRWU
Via this object stop and slat angle telegrams are sent.
OutputX
Wind Alarm
1 bit
CRWTU
This object indicates the current status of the wind alarm.
OutputX
Rain Alarm
1 bit
CRWTU
This object indicates the current status of the rain alarm.
OutputX
Frost Alarm
1 bit
CRWTU
This object indicates the current status of the frost alarm.
OutputX
Moving Status
1 bit
CRWTU
This object takes the value 1 while the shutter is moving up or down. Otherwise the value of the object is 0.
OutputX
Slat Position
1 byte
CRWU
This object is only visible when the “Type of function” is set to “Shutter/Blind”. Via this object it is possible to
set a position of the slat in
°.
OutputX
Blind Position
1 byte
CRWU
Via this object it is possible to set a position of the blind in %.
OutputX
Position Indication in %
1 bit
CRWTU
Via this object the current position of the shutter in % is indicated.
OutputX
Slat Angle Indication in
°
1 byte
CRT
This object is only visible when the “Type of function” is set to “Shutter/Blind”. Via this object the current
position of the slat in
° is indicated.
OutputX
Locking
1 bit
CRWU
This object is only visible when the locking function is enabled. Via the group address linked, it is possible
to lock the current output through the value configured previously.