Combo Output Module
Product Manual
©2017 INTERRA
65
PM131126001A
SPECIAL FUNCTIONS
PARAMETER
DESCRIPTION
VALUES
Behaviour During Bus Voltage
Failure
This parameter determines the behaviour of the
outputs during a bus voltage failure
No Reaction: There is no reaction; the outputs
remain the last state.
Switch Off All Outputs: The outputs are switched
off.
No Reaction
Switch
Off
All
Outputs
Behaviour After Bus Voltage
Return
This parameter determines the behaviour of the
outputs after a bus voltage failure.
No Reaction: There is no reaction; the outputs
remain the last state.
Switch Off All Outputs: The outputs are switched
off.
No Reaction
Switch
Off
All
Outputs
Feedback Telegram
This parameter is used to set weather the status
of the fan coil and the fan speed are shown.
Disabled: There is no information about the status
outputs.
Normal: The real status of the outputs is shown
via the corresponding communication objects.
Inverted: The inverted status of the fan coil is
shown via the “Feedback for Fan Coil Active”
communication object. The status of the fan
speed is shown normally even though this option
is used.
Disabled
Normal
Inverted
Feedback Startup Time Delay
This parameter set a delay between the startup
and the sending of the feedback telegram to the
bus.
‘Disabled” option means that there is not
emission of the telegram after the startup.
Disabled
5s, 10s, 30s, 1min,
5min,
10min,
20min.
30min,
40min, 50min, 1h,
2h, 3h, 4h, 5h, 6h,
12h, 24h.