Combo Output Module
Product Manual
©2017 INTERRA
23
PM131126001A
PARAMETER
DESCRIPTION
VALUES
No: A new ON telegram has no effect. The On
Delay time is not modified.
Yes: A new ON telegram reset the On Delay time
and it starts to count again each time that a new
telegram is received.
Working Hours Counter
This parameter allows counting the hours that the
output is operating as ON or OFF.
Disabled: This option is disabled.
Count Off Duration: The counter shows the time
during which the output is off.
Count On Duration: The counter shows the time
during which the output is on.
Disabled
Count Off Duration
Count On Duration
Count Direction
4
This parameter determines the direction of the
hours counter.
Increment: The counter starts from 0 and
increases incrementally.
Decrement: The counter starts from a value
which will be decreased.
Increment
Decrement
Set Point for Alert (hour)
4
This parameter set an alert value for hours
counter.
1000
(1...65535)
Periodic Sending of Working
Duration
4
This parameter determines the sending period of
the hours counter current value. “Disabled” option
means that the value of the hours counter is not
sent to the bus and it is necessary to read the
value to know it.
Disabled
5s, 10s, 30s, 1min,
5min,
10min,
20min,
30min,
40min, 50min, 1h.
2h, 3h, 4h, 5h, 6h,
12h, 24h.
Locking
This parameter determines if the output can be
locked via an additional locking object or not.
Disabled: This option is disabled.
Lock
On
Value
0:
When
the
locking
communication object takes the value 0, status
changes at the output are not transmitted.
Lock
On
Value
1:
When
the
locking
communication object takes the value 1, status
changes at the output are not transmitted.
Disabled
Lock On Value 0
Lock On Value 1
Output Status at Beginning of
Locking
5
This parameter determines the behaviour of the
lighting at the beginning of locking.
No Reaction/Last State: There is no reaction; the
lights remain the last value received.
OFF: The lights are switched off.
ON: The lights are switched on.
No Reaction/Last
State
OFF
ON