Combo Output Module
Product Manual
©2017 INTERRA
31
PM131126001A
5.2.1.
Parameters
CONFIGURATION
PARAMETER
DESCRIPTION
VALUES
Valve Protection
This parameter allows the valve to open
automatically for 5 min every 24h when the valve
is closed.
No
Periodically
Open
Valve 5-min every
24h
Summer/Winter Mode Switch
Over
This parameter provides an object which can be
used as summer/winter switch.
No
Yes
Summer/Winter Pol. (Normal:
Sum=0, Win=1)
1
This parameter determines the set value for each
mode.
Normal: Summer=0 / Winter=1.
Inverted: Summer=1 / Winter=0.
Normal
Inverted
Operation Mode at Startup
1
This parameter defines the operating mode at
startup.
No Reaction/Last
Mode
Summer Mode