Combo Output Module 

                                                                                                                          Product Manual 

 

©2017 INTERRA

  

26

 

 PM131126001A

 

SCENES 

 

 

PARAMETER 

DESCRIPTION 

VALUES 

Scene (1...16) 

This  parameter  allows  the  use  of  16  different 
scenes.  

Disabled 

Enabled 

Scene (1...16) Number 

This parameter is used to  assign  the number of 
the scene. 

1

 (1...64) 

Scene (1...16) State 

This  parameter  determines  the  status  of  the 
output for the current scene.  

OFF 

ON 

Scene 

(1...16) 

Storage 

Function 

This parameter is used to set whether the scene 
can be stored.  

OFF 

ON 

Scene (1...16) Delay  

This parameter set a delay between the call of the 
scene and the real action of the output. 

Value “0” 

means the immediate emission of the scene. 

0

 (0...255)

 

 

 

 

Содержание ITR504

Страница 1: ...2017 INTERRA ITR504 ITR508 ITR512 ITR516 ITR520 ITR524 4 8 12 16 20 or 24 Channels Combo Output Modules Product Manual...

Страница 2: ...disclaims all liability arising from this information and its use Use of Interra devices in life support and or safety applications is entirely at the buyer s risk and the buyer agrees to defend inde...

Страница 3: ...hesitate to contact us E mail iletisim interra com tr Tel 90 216 326 26 40 Fax 90 216 324 25 03 Most Current Product Manual To obtain the most up to date version of this product manual please visit o...

Страница 4: ...ram Name 4 8 12 16 20 or 24 Combo Output Module Product family Combo Output Module Product name 4 8 12 16 20 or 24 Combo Output Module Media Type Twisted Pair Order number ITR504 16A ITR508 16A ITR512...

Страница 5: ...100A inrush Mode of commissioning S Mode Type of protection IP 20 Temperature Range Operation 10 C 70 C Storage 25 C 100 C Maximum air humidity 90 RH Flammability Non flammable product Mounting DIN R...

Страница 6: ...HEATING 29 5 2 1 Parameters 31 5 2 2 Objects 35 5 3 SHUTTER BLIND 36 5 3 1 Parameters 40 5 3 2 Objects 46 5 4 SHUTTER BLIND 24V 47 5 5 FAN COILS 48 5 5 1 FAN COIL 2 PIPES 51 5 5 1 1 Parameters 52 5 5...

Страница 7: ...eration 49 Fig17 Scene Example 74 Fig18 Shutter Movement Duration 76 Fig19 Shutter Blind Movement Duration 76 Fig2 Staircase Function 18 Fig20 Slat Steps 77 Fig21 Connection Diagram Example Configurat...

Страница 8: ...ommunication of the devices via the KNX bus enables information exchanges with KNX sensors and the integration with a building management system The combo has been developed for providing the whole co...

Страница 9: ...ITR524 8 X Note The bold values in the tables are the factory settings default values Type and number of the available objects depend on the settings with ETS Visible objects might vary according to...

Страница 10: ...this option is enabled See the Appendix A Manual Control 2 1 PARAMETERS PARAMETER DESCRIPTION VALUES Module Alive Beacon This parameter allows sending the value true periodically while the module is r...

Страница 11: ...put is shown inversely Through the parameter Send Feedback On the type of feedback can be defined The combo actuator allows sending the result of logic gates when the logic output is changed or conver...

Страница 12: ...ermines the logic gate type The output will be true or false depending on the result of this logic Disabled This option is disabled The logic operations AND OR and XOR are possible for this function A...

Страница 13: ...akes the value off after a delay configured in this parameter 0 0 255 Cyclic Sending of Feedback This parameter determines the sending period of the logic output value Disabled option means that the f...

Страница 14: ...ifferent data values 4 1 PARAMETERS PARAMETER DESCRIPTION VALUES Converter Gate Count This parameter determines the number of converter gates to use No Converter Gate 1 Converter Gate 2 Converter Gate...

Страница 15: ...old value for the input when it is configured as 2 Byte Threshold 0 0 65535 Output Type This parameter determines the type of data for the logic output 1 Bit 2 Bits 1 Byte 2 Byte Output Value This par...

Страница 16: ...Combo Output Module Product Manual 2017 INTERRA 16 PM131126001A Via this object the current output of the converter is shown...

Страница 17: ...ng on the light it will remain ON for a configurable time TSF After this time the output switches off automatically Each time an ON telegram is received while the lights are ON the delay time is resta...

Страница 18: ...available for ITR520 and ITR524 FLASHING Via the Flashing communication object the output starts to flash as soon as the value ON is received The period TFI is previously configured in the Flashing I...

Страница 19: ...e values parameterized for the output concerned will be overwritten into the actuator It means that any change made by the user will be deleted Therefore it is important before any maintenance to know...

Страница 20: ...ailure a delay for the status feedback transmission at startup can be parameterized When this option is used the status of the output after a bus voltage failure is sent once the time delay configured...

Страница 21: ...VALUES Contact Type This parameter determines the type of contact output Normally Open The relay works as normally open contact Normally Close The relay works as normally close contact Normally Open...

Страница 22: ...ay Hours 0 23 3 Hours of On Delay 0 0 23 On Delay Minutes 0 59 3 Minutes of On Delay 0 0 59 On Delay Seconds 0 59 3 Seconds of On Delay 30 0 59 Off Delay Retriggerable1 This parameter allows the stair...

Страница 23: ...ert value for hours counter 1000 1 65535 Periodic Sending of Working Duration4 This parameter determines the sending period of the hours counter current value Disabled option means that the value of t...

Страница 24: ...min 10min 20min 30min 40min 50min 1h 2h 3h 4h 5h 6h 12h 24h Feedback Periodical Sending6 This parameter determines the sending period of the output current value Disabled option means that the feedbac...

Страница 25: ...Combo Output Module Product Manual 2017 INTERRA 25 PM131126001A...

Страница 26: ...er is used to assign the number of the scene 1 1 64 Scene 1 16 State This parameter determines the status of the output for the current scene OFF ON Scene 1 16 Storage Function This parameter is used...

Страница 27: ...to 0 ON The output is forced to 1 No Reaction Last State OFF ON Logic Function This parameter provides a logic object which is logically linked with the ON OFF object when this option is enabled The o...

Страница 28: ...ameter is configured as Decrement the starting value for the countdown is sent via this object too OutputX Reset Counter 1 bit CRWTU This object is only visible when the Working Hours Counter function...

Страница 29: ...r than the upper limit The hysteresis value is the result of the subtraction between Upper Limit and Lower Limit In the next example the Upper Limit 25 and the Lower Limit 15 It means that the hystere...

Страница 30: ...the period configured Additionally to reduce the bus traffic after any failure a delay for the status feedback transmission at startup can be parameterized When this option is used the status of the...

Страница 31: ...sed No Periodically Open Valve 5 min every 24h Summer Winter Mode Switch Over This parameter provides an object which can be used as summer winter switch No Yes Summer Winter Pol Normal Sum 0 Win 1 1...

Страница 32: ...he output to go back to off It must be a value smaller than the upper limit 10 0 100 Upper Limit 2 This value set the value of the valve opening It must be a value greater than 0 10 0 100 Forced Posit...

Страница 33: ...1h 2h 3h 4h 5h 6h 12h 24h Feedback Periodical Sending4 This parameter determines the sending period of the output current value Disabled option means that the feedback telegram is sent only after outp...

Страница 34: ...odule Product Manual 2017 INTERRA 34 PM131126001A 3These parameters are only visible when the parameter Forced Position is enabled 4These parameters are only visible when the parameter Feedback Telegr...

Страница 35: ...s on or off OutputX Manipulated Value 1 byte CRWU This object is only visible when the Type of Manipulated Variable is set to Continuous 1 Byte Via this object the valve is controlled with percentages...

Страница 36: ...ilable In contrast to the shutter function when the blind is at rest the telegrams received via the object Slat Angle Stop allow the positioning of the slats Slat Angle Stop When the positioning of th...

Страница 37: ...0 180 This parameter determines the number of steps required to move the slats from the 0 position to the 180 position The time of these steps is configured through the parameter Duration of Short Mov...

Страница 38: ...via the object scene must be 23 On the other hand the value 152 128 23 must be sent for storage the scene number 24 The recall of each scene can be delayed whether a time delay has been defined previo...

Страница 39: ...Combo Output Module Product Manual 2017 INTERRA 39 PM131126001A No Reaction Last State There is no action on the outputs UP The shutter goes up DOWN The shutter goes down...

Страница 40: ...n Movement Duration sec This parameter set the time of the down shutter movement duration 120 0 255 Duration of Short Movement x50ms This parameter set the time for the short movements when the shutte...

Страница 41: ...parameter determines the behaviour of the shutter at the beginning of locking No Reaction There is no reaction the shutter remains the last state Up The shutter goes up Down The shutter goes down No R...

Страница 42: ...ns that the feedback telegram is sent only after output changes not periodically Disabled 5s 10s 30s 1min 5min 10min 20min 30min 40min 50min 1h 2h 3h 4h 5h 6h 12h 24h 1This parameter is only visible w...

Страница 43: ...osition Value 0 100 This parameter set the position of the shutter for a particular scene 0 0 100 Scene 1 16 Slat Angle Value 0 180 This parameter set the slat angle value for a particular scene 0 0 1...

Страница 44: ...hutter when a wind alarm is ended No Reaction The shutter remains the last state Up The shutter is upped Down The shutter is lowered Value It is possible to define a position value in No Reaction Up D...

Страница 45: ...hen a frost alarm occurs No Reaction The shutter remains the last state Up The shutter is upped Down The shutter is lowered Value It is possible to define a position value in No Reaction Up Down Value...

Страница 46: ...OutputX Moving Status 1 bit CRWTU This object takes the value 1 while the shutter is moving up or down Otherwise the value of the object is 0 OutputX Slat Position 1 byte CRWU This object is only visi...

Страница 47: ...47 PM131126001A 5 4 SHUTTER BLIND 24V The application description for Shutter Blind 24v is the same as Shutter Blind The unique difference between these two options is the number of outputs needed 2...

Страница 48: ...is increased in steps Depending on the command value 1 byte whose value comes from the thermostat or room master the combo determines the corresponding fan speeds via configurable threshold values He...

Страница 49: ...g functions is used and return to the automatic mode is required it is necessary to use the Return to Automatic Mode object When this object takes the value 1 every forced are disabled and the system...

Страница 50: ...action of the output during bus voltage failure can be configured too The combo actuator allows two different behaviours for bus voltage failure No Reaction There is no reaction the outputs remain the...

Страница 51: ...hich is supplied centrally Heating Cooling In this system only one water circuit is available for heating and cooling Depending on the central system warm or cold water is supplied to the pipe system...

Страница 52: ...nly Cooling Heating Cooling Fan Control Behaviour This parameter is used to set how the fan coil fan speed is controlled Only One Fan Output at the Same Time Each fan speed is controlled individually...

Страница 53: ...rameter set the low threshold value for the fan 3 70 1 100 Hysteresis for Fan Limit 0 20 This parameter determines the hysteresis for fan limits This value is proportional to the limits configured pre...

Страница 54: ...ion of the function Switch Off All Outputs The outputs are switched off Operation with Fan Level The fan speed is set to a value configured in the next parameter No Reaction Switch Off All Outputs Ope...

Страница 55: ...Product Manual 2017 INTERRA 55 PM131126001A PARAMETER DESCRIPTION VALUES take the values according to the last command received Note If during the disabling the operating mode is changed it is always...

Страница 56: ...ched off No Reaction Switch Off All Outputs Feedback Telegram This parameter is used to set weather the status of the fan coil and the fan speed are shown Disabled There is no information about the st...

Страница 57: ...ut changes not periodically Disabled 5s 10s 30s 1min 5min 10min 20min 30min 40min 50min 1h 2h 3h 4h 5h 6h 12h 24h Feedback Type This parameter defines the type of feedback for the fan speed Fan level...

Страница 58: ...n the Feedback Type parameter is set to Fan Levels Individually Via the group address linked it indicates the current status of the fan speed 2 OutputX Feedback for Fan Level 3 1 bit CRWTU This object...

Страница 59: ...peed regardless of the real operating percentage OutputX Constant Fan Level 1 Bit 1 bit CRWTU Via this object a constant level for the fan speed can be defined through the sending of consecutive value...

Страница 60: ...ge Over Object a new communication object is added Heating Cooling Change Over which defines the operating mode of the fan coil With the normal configuration when this object takes the value 0 the fan...

Страница 61: ...determined by the command value The fancoil works taking into account the last value received via Command Value for Heating or Command Value for Cooling objects Change Over Object Command Value Heatin...

Страница 62: ...rameter set the low threshold value for the fan 1 5 1 100 Fan 2 Lower Limit 1 100 This parameter set the low threshold value for the fan 2 30 1 100 Fan 3 Lower Limit 1 100 This parameter set the low t...

Страница 63: ...ion of the function Switch Off All Outputs The outputs are switched off Operation with Fan Level The fan speed is set to a value configured in the next parameter No Reaction Switch Off All Outputs Ope...

Страница 64: ...Product Manual 2017 INTERRA 64 PM131126001A PARAMETER DESCRIPTION VALUES take the values according to the last command received Note If during the disabling the operating mode is changed it is always...

Страница 65: ...ched off No Reaction Switch Off All Outputs Feedback Telegram This parameter is used to set weather the status of the fan coil and the fan speed are shown Disabled There is no information about the st...

Страница 66: ...ut changes not periodically Disabled 5s 10s 30s 1min 5min 10min 20min 30min 40min 50min 1h 2h 3h 4h 5h 6h 12h 24h Feedback Type This parameter defines the type of feedback for the fan speed Fan level...

Страница 67: ...ype parameter is set to Fan Levels Individually Via the group address linked it indicates the current status of the fan speed 2 OutputX Feedback for Fan Level 3 1 bit CRWTU This object is only visible...

Страница 68: ...tX Constant Fan Level 1 Bit 1 bit CRWTU Via this object the fan speed can be forced to a certain level through the sending of consecutive values When this object takes the value 1 consecutively the fa...

Страница 69: ...ented via the status led and is transmitted to the bus via the status object SHUTTER BLIND Shutter and blinds can be lowered or raised with a long push button action while a short push button action e...

Страница 70: ...0 0 1 1 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 Function Input 1 Input 2 Input 3 Input 4 Output OR 0 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 0 0 0 0...

Страница 71: ...odule Product Manual 2017 INTERRA 71 PM131126001A XOR 0 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 0 0 0 0 1 1 1 1 0 0 0 0 1 1 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 1 0 1 0 0 1 1...

Страница 72: ...The activation of the scene involves the following actions The shutter is positioned to 50 and 90 25 seconds after scene recall the light 1 is switched off 30 seconds after scene recall the light 2 is...

Страница 73: ...KNX devices in a scene The value of the scene can be modified through the storage option In the above example the light 2 is switched on recalling the scene 24 If it is required that the light 2 is sw...

Страница 74: ...e shutter starts to move from that position to the completely opened position On the contrary for measuring the down movement duration the shutter should be positioned to the completely opened positio...

Страница 75: ...the 180 position For measuring this number of steps the slats should be positioned to the completely closed position 0 and then start to move the slats step by step and counting them at the same time...

Страница 76: ...TR520 4 1 6 7 12 13 18 and 19 20 ITR524 4 1 6 7 12 13 18 and 19 24 Example Out 1 2 3 4 configured as fan coil 2 pipes This allows configuring the output 5 and 6 as shutter blind or lighting and heatin...

Страница 77: ...HEATING Out 4 LIGHTING HEATING Out 5 LIGHTING Out 6 LIGHTING HEATING Out 1 HEATING Out 2 LIGHTING HEATING Out 3 HEATING Out 4 LIGHTING HEATING Out 5 HEATING Out 6 LIGHTING HEATING Out 1 HEATING Out 2...

Страница 78: ...UTTER BLIND Out 1 2 3 4 SHUTTER BLIND 24V Out 5 LIGHTING Out 6 LIGHTING HEATING Out 1 2 3 4 SHUTTER BLIND 24V Out 5 HEATING Out 6 LIGHTING HEATING Out 1 2 3 4 SHUTTER BLIND 24V Out 5 6 SHUTTER BLIND O...

Страница 79: ...HEATING Out 2 LIGHTING Out 8 LIGHTING Out 3 HEATING Out 9 HEATING Out 4 HEATING Out 10 HEATING Out 5 LIGHTING Out 11 LIGHTING Out 6 HEATING Out 12 LIGHTING Fig21 Connection Diagram Example Configurat...

Страница 80: ...Example Configuration 2 The combo module only allows configuring the first inputs as fancoil 2 or 4 pipes In the example above the inputs C1 C4 are used for the connection of a 2 pipes fancoil and th...

Страница 81: ...onnection Diagram Example Configuration 3 Every output of the combo module can be configured as shutter blind provided that 2 consecutive outputs are available However for the shutter blind 24V config...

Страница 82: ...your favourite Internet browser the web site contains the following information Overview of Interra Technology company and values Information about our products and projects Product Support Data shee...

Отзывы: