PolyGard

®

 CL

2

 Gas Transmitter

User Manual - AT-1193 

Page 08

6.3  Exchange of Sensor Element

 

Consider static electricity  See point 3. 
Sensor should always be installed without power applied: 

Unplug basic PCB AT03 carefully from the bottom part.

Unplug old sensor element from the PCB.

Take the new sensor out of the original packing.

Plug the sensor element in the PCB.

Replug the PCB AT03 in the terminal blocks X4, X5 carefully.

Calibrate according to section 5.

7 Troubleshooting

 

7.1  Analog Mode

 

Trouble

 

Cause

 

Solution

 

Output signal < 3 mA / 1,5 V 

and/or control voltage < 30 mV 

Jumper 0-20 % not set 

Check jumper position 
Measure tension at X4:

only for starting signal 2V/4 mA  Power voltage not applied

Two-wire: Pin 1 (+) and 4 (-) 

Three-wire: Pin 1 (+) and 2 (-) 

PCB AT03 not plugged in correctly at X4 

and X5 

Replug PCB correctly 

Wire break 

Check the wiring 

Output signal > 22 mA /220 mV  Short-circuit 

Check the wiring 

Control voltage does not reach 

the calculated value 

Sensor element not calibrated 

Calibrate sensor element 

Sensor sensitivity < 30 % 

Replace sensor element 

No reaction of the output signal 

in spite of gas concentration 

Power voltage not applied 

Measure tension at X4 

Signal (Pin 4) not wired correctly 

Check the wiring 

8  Cross-sensitivity Data

 

The cross sensitivity can be read from the table Technical Data (see section 9). The table doesn’t claim to 

be complete. Other gases can have an influence on the sensitivity, too. The indicated sensitivity data 

are only standard values referring to new sensor elements. 

Specifications subject to change without notice. | USA 140403 | Page 8 of 13

12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.IN

TEC

 | relevantsolutions.com/inteccontrols

AT-1193 – UserManual

Polygard® is a registered trademark of MSR | GAADT531193_E_1011.pdf

Specifications subject to change without notice. | USA 160104 | Page 8 of 13

12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.IN

TEC

 | relevantsolutions.com/inteccontrols

AT-1193 – UserManual

PolyGard

®

 is a registered trademark of MSR-Electronic GmbH | GAADT531193_E_1011

INTEC Controls | 12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.INTEC | inteccontrols.com

Specifications subject to change without notice. | GAADT531193_E_1011 | USA 200211 | Page 8 of 13

AT-1193 V3 – UserManual

Содержание AT03-005

Страница 1: ...Specifications subject to change without notice USA 140403 Page 1 of 13 12700 Stowe Drive Suite 100 Poway CA 92064 Ph 858 578 7887 888 GO INTEC relevantsolutions com inteccontrols AT 1193 UserManual...

Страница 2: ...8 7 Troubleshooting 8 7 1 Analog Mode 8 8 Cross sensitivity Data 8 9 Technical Data 9 10 Figures 11 11 Part Disposal 13 12 Notes and General Information 13 12 1 Intended Product Application 13 12 2 I...

Страница 3: ...uses through a membrane filter into the liquid electrolyte of the sensor The chemical process of the measurement is one of reduction where one molecule of the target gas is exchanged for one molecule...

Страница 4: ...only in a duct system with a maximum air velocity of 10 m s 2000 ft min or less Mounting must be performed so that the probe openings are in line with the airflow 3 2 Installation Open the cover Unpl...

Страница 5: ...tion Please observe proper handling procedures for test gas bottles Attention CL2 calibration gas is toxic never inhale the gas Symptoms Chemical burn dizziness headache and nausea Procedure if expose...

Страница 6: ...il the signal is stable adjust control voltage with potentiometer Gain until the signal corresponds to the calculated value 2 mV see 5 3 3 Calculation of Control Voltage Remove calibration adapter wit...

Страница 7: ...etermined by the person responsible for the gas warning system according to the legal requirements INTEC Controls recommends checking the PolyGard Transmitter every three months and maintaining it eve...

Страница 8: ...ring Control voltage does not reach the calculated value Sensor element not calibrated Calibrate sensor element Sensor sensitivity 30 Replace sensor element No reaction of the output signal in spite o...

Страница 9: ...2 5 Electrical Power supply 18 28 VDC AC reverse polarity protected 2 wire mode only VDC Power consumption without options Analog mode 22 mA max 0 6 VA Output signal Analog output signal Selectable Cu...

Страница 10: ...8 EEC CE Approvals Enclosure Type A UL 508A Warranty Two years material and workmanship 12 months normal exposure for sensor element Options Relay output Alarm relay 1 switching threshold 5 ppm 30 VAC...

Страница 11: ...C Do not connect power supply at this pin 0 VDC 24 VAC or 0VAC will destroy the transmitter 0 VAC DC 24 VAC DC Do not connect 24 VAC at pin 2 and pin 4 or 24 VDC at pin 2 and 0 VDC at pin 4 Short circ...

Страница 12: ...ut V DC mA Anal Output Start Point 20 0 Function Relay R2 NO NC NC NO Manual Calibration 5 4 3 2 1 1 2 3 4 5 6 7 X5 X4 Specifications subject to change without notice USA 140403 Page 12 of 13 12700 St...

Страница 13: ...lectrical Code ANSI NFPA70 It is also essential to follow strictly all instructions as provided in the user manual 12 3 Maintenance It is recommended to check the PolyGard transmitter regularly Due to...

Отзывы: