background image

Customer Services (858) 578-7887 & (888) GO IN

TEC

IN

TEC

 Controls, 12700 Stowe Dr., Suite 1

0

0, Poway, CA 92064

Fax (858) 578-4633 & (888) FX IN

TEC

www.inteccontrols.com

Specification subject to change without notice.

Printed in USA 140403

Polygard® is a registered trademark of MSR

GAADT531193_E_1011.pdf

PolyGard

®

 CL

2

 Gas Transmitter

User Manual - AT-1193 

Page 05

4.1  Wiring Connection

 

Open the cover. Unplug basic PCB carefully from terminal blocks X4 and X5.

Insert the cable and connect cable leads to terminal blocks. See fig. 1.

Replug the PCB in the terminal blocks X4, X5 with care. Replace the cover.

Note: The connection of the power supply at the output signal (X4 pin 4) can destroy the transmitter.

 

5 Commissioning

 

Consider commissioning instructions at any exchange of the sensor element as well. 
Only trained technicians should perform the following: 

Check mounting location.

Select output signal form: Current or voltage, and starting point 0 or 20%. See fig. 4.

Check power voltage.

Check PCB AT03 for correct mounting at X4 and X5.

Required instruments for commissioning (calibration) of the transmitter: 

Test gas bottle with synthetic air (20 % O

2

, 80 % N) or chlorine-free ambient air.

Test gas bottle with Cl

(ppm) in the range of 30 – 70 % of the measuring range. Rest is synthetic air.

Gas pressure regulator with flow meter to control the gas flow to 150 ml/min.

Calibration adapter with tube. Calibration set CONKIT-E/CH-AT. See fig. 5.

Digital voltmeter with range 0 – 300 mV, accuracy 1%.

Small screwdriver.

Note:

 

Prior to calibration the sensor must be connected to the power supply and fully stabilized for at least 6 

hours without interruption. 
Please observe proper handling procedures for test gas bottles! 

Attention: 

CL

calibration gas is toxic, never inhale the gas 

Symptoms: Chemical burn, dizziness, headache and nausea. 

Procedure if exposed: Take the victim into fresh air at once, call a doctor. 

5.1  Correction of the Zero-point at the Analog Output Signal

 

The analog output signal is factory set to the zero-point. If necessary, a manual adaptation of the analog 

signal is possible within 10 sec. after having applied the supply voltage. 

Jumper 0-20 % for signal start has to be set (= 4 mA or 2 V).

Connect digital voltmeter (300 mV) at test pint “Test” (measuring signal ~ 40 mV = 4.0 mA).

Switch on the operating voltage.

Each pressing on the “Zero” push-button increases the signal by + 0.5 mV (0.05 mA). Press the

button  repeatedly until the measuring signal reaches 40 ± 0.2 mV. After 44mV the signal starts

again at 36 mV. The correction is only possible within the 10 seconds after having switched on the

power supply.  An impulse pause of more than 10 sec. cancels the release of the correction

function.

Specifications subject to change without notice. | USA 140403 | Page 5 of 13

12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.IN

TEC

 | relevantsolutions.com/inteccontrols

AT-1193 – UserManual

Polygard® is a registered trademark of MSR | GAADT531193_E_1011.pdf

Specifications subject to change without notice. | USA 160104 | Page 5 of 13

12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.IN

TEC

 | relevantsolutions.com/inteccontrols

AT-1193 – UserManual

PolyGard

®

 is a registered trademark of MSR-Electronic GmbH | GAADT531193_E_1011

INTEC Controls | 12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.INTEC | inteccontrols.com

Specifications subject to change without notice. | GAADT531193_E_1011 | USA 200211 | Page 5 of 13

AT-1193 V3 – UserManual

Содержание AT03-005

Страница 1: ...Specifications subject to change without notice USA 140403 Page 1 of 13 12700 Stowe Drive Suite 100 Poway CA 92064 Ph 858 578 7887 888 GO INTEC relevantsolutions com inteccontrols AT 1193 UserManual...

Страница 2: ...8 7 Troubleshooting 8 7 1 Analog Mode 8 8 Cross sensitivity Data 8 9 Technical Data 9 10 Figures 11 11 Part Disposal 13 12 Notes and General Information 13 12 1 Intended Product Application 13 12 2 I...

Страница 3: ...uses through a membrane filter into the liquid electrolyte of the sensor The chemical process of the measurement is one of reduction where one molecule of the target gas is exchanged for one molecule...

Страница 4: ...only in a duct system with a maximum air velocity of 10 m s 2000 ft min or less Mounting must be performed so that the probe openings are in line with the airflow 3 2 Installation Open the cover Unpl...

Страница 5: ...tion Please observe proper handling procedures for test gas bottles Attention CL2 calibration gas is toxic never inhale the gas Symptoms Chemical burn dizziness headache and nausea Procedure if expose...

Страница 6: ...il the signal is stable adjust control voltage with potentiometer Gain until the signal corresponds to the calculated value 2 mV see 5 3 3 Calculation of Control Voltage Remove calibration adapter wit...

Страница 7: ...etermined by the person responsible for the gas warning system according to the legal requirements INTEC Controls recommends checking the PolyGard Transmitter every three months and maintaining it eve...

Страница 8: ...ring Control voltage does not reach the calculated value Sensor element not calibrated Calibrate sensor element Sensor sensitivity 30 Replace sensor element No reaction of the output signal in spite o...

Страница 9: ...2 5 Electrical Power supply 18 28 VDC AC reverse polarity protected 2 wire mode only VDC Power consumption without options Analog mode 22 mA max 0 6 VA Output signal Analog output signal Selectable Cu...

Страница 10: ...8 EEC CE Approvals Enclosure Type A UL 508A Warranty Two years material and workmanship 12 months normal exposure for sensor element Options Relay output Alarm relay 1 switching threshold 5 ppm 30 VAC...

Страница 11: ...C Do not connect power supply at this pin 0 VDC 24 VAC or 0VAC will destroy the transmitter 0 VAC DC 24 VAC DC Do not connect 24 VAC at pin 2 and pin 4 or 24 VDC at pin 2 and 0 VDC at pin 4 Short circ...

Страница 12: ...ut V DC mA Anal Output Start Point 20 0 Function Relay R2 NO NC NC NO Manual Calibration 5 4 3 2 1 1 2 3 4 5 6 7 X5 X4 Specifications subject to change without notice USA 140403 Page 12 of 13 12700 St...

Страница 13: ...lectrical Code ANSI NFPA70 It is also essential to follow strictly all instructions as provided in the user manual 12 3 Maintenance It is recommended to check the PolyGard transmitter regularly Due to...

Отзывы: