PolyGard

®

 CL

2

 Gas Transmitter

User Manual - AT-1193 

Page 06

5.2 Calibration

 

Manual  calibration  is  only  possible  if  the  transmitter  is  equipped  with  the  push-button  “Zero”  and 

the  potentiometer “Gain” (= version for manual calibration). 

5.2.1 Zero-point

 

Connect digital voltmeter to pin “Test”.

Connect calibration adapter carefully to the sensor element.

Apply synthetic air (150 ml/min; 1 Bar (14.5 psi) ± 10%), or Chlorine (Cl

2

)-free ambient air.

Wait 2 minutes until the signal is stable, push button “Zero” for 5 seconds.

After  successful  calibration  the  measuring  signal  is  corrected  automatically.  Depending  on 

the selected signal starting point the measuring signal shows the following values: 

Signal start at 2 V or 4 mA 

40 mV = 0 ppm 

Signal start at 0 V or 0 mA 

0 mV   = 0 ppm 

If the zero-point is out of the admissible range (> 20 mV at starting point 0% / > 60 mV at 

starting  point 20%) before calibration, there is no correction of the measuring signal. The 

sensor has to be replaced. 

Remove calibration adapter carefully by turning lightly. Check the sensor for correct mounting

5.3.2 Gain

 

Connect digital voltmeter to pin “Test”.

Connect calibration adapter carefully to the sensor element.

Apply calibration test gas Cl

(150 ml/min; 1 Bar (14.5 psi) ± 10%).

Wait three minutes until the signal is stable, adjust control voltage with potentiometer ”Gain” until

the signal corresponds to the calculated value ± 2 mV, see “5.3.3 Calculation of Control Voltage”.

Remove calibration adapter with a careful light turn. Check the sensor for correct mounting

By limiting the gain factor, calibration will not be possible any more when the sensitivity of the

sensor reaches a residual sensitivity of 30 %. Then the sensor has to be replaced.

5.3.3  Calculation of Control Voltage

 

Signal start 2 V / 4 mA

 

Control voltage (mV) 

160 (mV) x test gas concentration Cl

(ppm)  +  40 (mV) 

measuring range Cl

(ppm) 

Signal start 0 V / 0 mA

 

Control voltage (mV) 

200 (mV) x test gas concentration Cl

(ppm) 

measuring range Cl

(ppm) 

Example:

 

Measuring range 

20 ppm 

Test gas concentration 

10 ppm Cl

Control voltage: Signal start 2 V / 4 mA 

120 mV 

Control voltage: Signal start 0 V / 0 mA 

100 mV 

Signal start 2 V / 4 mA 

Signal start 0 V / 0 mA

 

160 (mV) x 10 (ppm)  + 40 (mV)   =   120 mV 

200 (mV) x 10 (ppm)  =   100 

mV 20 (ppm) 

20 (ppm) 

Specifications subject to change without notice. | USA 140403 | Page 6 of 13

12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.IN

TEC

 | relevantsolutions.com/inteccontrols

AT-1193 – UserManual

Polygard® is a registered trademark of MSR | GAADT531193_E_1011.pdf

Specifications subject to change without notice. | USA 160104 | Page 6 of 13

12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.IN

TEC

 | relevantsolutions.com/inteccontrols

AT-1193 – UserManual

PolyGard

®

 is a registered trademark of MSR-Electronic GmbH | GAADT531193_E_1011

INTEC Controls | 12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.INTEC | inteccontrols.com

Specifications subject to change without notice. | GAADT531193_E_1011 | USA 200211 | Page 6 of 13

AT-1193 V3 – UserManual

Содержание AT03-005

Страница 1: ...Specifications subject to change without notice USA 140403 Page 1 of 13 12700 Stowe Drive Suite 100 Poway CA 92064 Ph 858 578 7887 888 GO INTEC relevantsolutions com inteccontrols AT 1193 UserManual...

Страница 2: ...8 7 Troubleshooting 8 7 1 Analog Mode 8 8 Cross sensitivity Data 8 9 Technical Data 9 10 Figures 11 11 Part Disposal 13 12 Notes and General Information 13 12 1 Intended Product Application 13 12 2 I...

Страница 3: ...uses through a membrane filter into the liquid electrolyte of the sensor The chemical process of the measurement is one of reduction where one molecule of the target gas is exchanged for one molecule...

Страница 4: ...only in a duct system with a maximum air velocity of 10 m s 2000 ft min or less Mounting must be performed so that the probe openings are in line with the airflow 3 2 Installation Open the cover Unpl...

Страница 5: ...tion Please observe proper handling procedures for test gas bottles Attention CL2 calibration gas is toxic never inhale the gas Symptoms Chemical burn dizziness headache and nausea Procedure if expose...

Страница 6: ...il the signal is stable adjust control voltage with potentiometer Gain until the signal corresponds to the calculated value 2 mV see 5 3 3 Calculation of Control Voltage Remove calibration adapter wit...

Страница 7: ...etermined by the person responsible for the gas warning system according to the legal requirements INTEC Controls recommends checking the PolyGard Transmitter every three months and maintaining it eve...

Страница 8: ...ring Control voltage does not reach the calculated value Sensor element not calibrated Calibrate sensor element Sensor sensitivity 30 Replace sensor element No reaction of the output signal in spite o...

Страница 9: ...2 5 Electrical Power supply 18 28 VDC AC reverse polarity protected 2 wire mode only VDC Power consumption without options Analog mode 22 mA max 0 6 VA Output signal Analog output signal Selectable Cu...

Страница 10: ...8 EEC CE Approvals Enclosure Type A UL 508A Warranty Two years material and workmanship 12 months normal exposure for sensor element Options Relay output Alarm relay 1 switching threshold 5 ppm 30 VAC...

Страница 11: ...C Do not connect power supply at this pin 0 VDC 24 VAC or 0VAC will destroy the transmitter 0 VAC DC 24 VAC DC Do not connect 24 VAC at pin 2 and pin 4 or 24 VDC at pin 2 and 0 VDC at pin 4 Short circ...

Страница 12: ...ut V DC mA Anal Output Start Point 20 0 Function Relay R2 NO NC NC NO Manual Calibration 5 4 3 2 1 1 2 3 4 5 6 7 X5 X4 Specifications subject to change without notice USA 140403 Page 12 of 13 12700 St...

Страница 13: ...lectrical Code ANSI NFPA70 It is also essential to follow strictly all instructions as provided in the user manual 12 3 Maintenance It is recommended to check the PolyGard transmitter regularly Due to...

Отзывы: