Humidity Calibration Mode
1) Once in Factory Setup Mode, press the Sensor button
2) Press the Up or Down button to select the current humidity level
The display will appear similar to the following
The top numbers represent:
40
What the humidity sensor sees
-92
or
17
the offset from current reading
The offset is from -10 to +10
The displayed number needs to be multiplied by 0.1 to get the actual offset
Factory Reset to Default
Factory Reset Changes
INSTEON is reset (all links removed)
Day / time is changed to 12:00, Monday
Programming times and temperatures are reset to their default
Factory Reset Does Not Change
Temperature
offset
Humidity
Offset
F or C setting
Option 1
1) Remove power, press and hold Set button while powering up
2) Continue pressing and holding for ~10 seconds
Device will blink all segments and do continuous (Beep) during 10 seconds
3) When blinking / buzzing stops, release Set button
Device goes into factory reset for ~10 seconds
Screen goes blank, LEDs off
At completion display will briefly show a reset status code:
00 = successful reset