39
For 21k,24k models:
1) Defrosting condition:
AC will enter defrosting mode if any of the following items is satisfied.
(1) When T3
TC1 , if the
compressor keeps running over 40 minutes and T3
TC3 for 3
minutes.
(2) After the last defrosting, the time that the outdoor fan is off but the compressor is on in high T2
protection cumulates up to 90 minutes.
2) Condition of ending defrosting:
If any one of the following items is satisfied, the defrosting will terminate and the machine will turn to
normal heating mode.
(1)T3 rises to be higher than TC2.
(2)The machine has run for 10 minutes in defrosting.
3) Defrosting action
8.4.5 Auto-mode
This mode can be chosen by remote controller and the setting temperature can be changed between
17~30 .
In auto mode, the machine will choose cooling, heating or fan-only mode according to the difference
between T1 and Ts.
For MSR1-18CR-NB6,
MSR1-22HRN1-NB8W models:
T1-Ts
Running mode
T1-Ts
2
Cooling
-3
T1-Ts +2
Fan-only
T1-Ts
-3
Heating (For cooling only model, it will run at Fan-only mode)
Содержание Oasis WOE10C2DB1 / HOE10C2MR83
Страница 10: ...8 Model W H D WOE10C2DB8 710 250 189 WOE13C2DB8 790 275 196 WOE18C2DB8 930 275 198 WOE24C2DB8 1036 315 230 ...
Страница 14: ...12 5 Wiring Diagram 5 1 Indoor Units WOE10C2DB8 WOE13C2DB8 WOE18C2DB8 WOE24C2DB8 ...
Страница 15: ...13 5 2 Outdoor Units HOE10C2MR83 HOE13C2MR83 HOE18C2MR83 ...
Страница 16: ...14 HOE24C2MR83 ...
Страница 46: ...44 9 2 Diagnosis and Solution 9 2 1 Indoor fan speed has been out of control diagnosis and solution ...
Страница 48: ...46 9 2 2 Open circuit or short circuit of temperature sensor diagnosis and solution ...
Страница 49: ...47 9 2 3 Over current protection occurs 4 times diagnosis and solution ...
Страница 51: ...49 9 2 6 Indoor outdoor units communication error diagnosis and solution ...