![innovair Oasis WOE10C2DB1 / HOE10C2MR83 Скачать руководство пользователя страница 39](http://html.mh-extra.com/html/innovair/oasis-woe10c2db1-hoe10c2mr83/oasis-woe10c2db1-hoe10c2mr83_service-manual_2063494039.webp)
37
Defrosting actions
During the defrosting mode, if the machine stopped or transferred to other mode, the defrosting mode
will stop, and all the defrosting conditions will be cleared.
For MSR1-22HRN1-NB8W model:
Defrosting starts when either of the following
&
:
A and B1 or A and B2 are satisfied:
A: The compressor keeps running for 45 minutes or more.
B1: The compressor keeps running for 45-120 minutes, and the temperature difference of evaporator
and room temperature meets one of the following:
B2: The compressor keeps running for 120 minutes or more, and the temperature difference of
evaporator and room temperature meets one of the following:
If the accumulated time of outdoor fan stopped but the compressor keep working in evaporator high
temperature protection mode reaches 90 minutes from the end of last defrosting mode.
Содержание Oasis WOE10C2DB1 / HOE10C2MR83
Страница 10: ...8 Model W H D WOE10C2DB8 710 250 189 WOE13C2DB8 790 275 196 WOE18C2DB8 930 275 198 WOE24C2DB8 1036 315 230 ...
Страница 14: ...12 5 Wiring Diagram 5 1 Indoor Units WOE10C2DB8 WOE13C2DB8 WOE18C2DB8 WOE24C2DB8 ...
Страница 15: ...13 5 2 Outdoor Units HOE10C2MR83 HOE13C2MR83 HOE18C2MR83 ...
Страница 16: ...14 HOE24C2MR83 ...
Страница 46: ...44 9 2 Diagnosis and Solution 9 2 1 Indoor fan speed has been out of control diagnosis and solution ...
Страница 48: ...46 9 2 2 Open circuit or short circuit of temperature sensor diagnosis and solution ...
Страница 49: ...47 9 2 3 Over current protection occurs 4 times diagnosis and solution ...
Страница 51: ...49 9 2 6 Indoor outdoor units communication error diagnosis and solution ...