38
8.4.3.4.2 Defrosting time
condition
runtime
minute
Defrosting time
minute
Case 1
A
B1
runtime 60
DT1
Case 2
A
B1
60
runtime 80
DT1+1
Case 3
A
B1
80
runtime 95
DT1+2
Case 4
A
B1
95
runtime 110
DT1+3
Case 5
A
B1
110
runtime 120
DT1+4
Case 6
A
B2
DT1+5
Case 7
DT1+5
At condition
, If item B is satisfied before item A, it would be regarded as severe frosting and the
defrosting time is 10 minutes.
After three times continuous condition
defrost, the fourth defrost time should be DT1 +5 minutes.
The air conditioner can't run on defrosting mode until the compressor has run for no less than 6.5
minutes.
8.4.3.4.3 Ending condition of defrosting
If one of following conditions is satisfied, end the defrost and turn into heating mode:
A. The defrost time has ended
B. The compressor current has reached to I
DEFROST
or above lasting 7 seconds, I
DEFROST
differs in
different models
8.4.3.4.4 Defrosting Actions
Compressor
4-Way valve
Outdoor fan
Indoor fan
25S
25S
20S
20S
10S
Defrosting time
Содержание Oasis WOE10C2DB1 / HOE10C2MR83
Страница 10: ...8 Model W H D WOE10C2DB8 710 250 189 WOE13C2DB8 790 275 196 WOE18C2DB8 930 275 198 WOE24C2DB8 1036 315 230 ...
Страница 14: ...12 5 Wiring Diagram 5 1 Indoor Units WOE10C2DB8 WOE13C2DB8 WOE18C2DB8 WOE24C2DB8 ...
Страница 15: ...13 5 2 Outdoor Units HOE10C2MR83 HOE13C2MR83 HOE18C2MR83 ...
Страница 16: ...14 HOE24C2MR83 ...
Страница 46: ...44 9 2 Diagnosis and Solution 9 2 1 Indoor fan speed has been out of control diagnosis and solution ...
Страница 48: ...46 9 2 2 Open circuit or short circuit of temperature sensor diagnosis and solution ...
Страница 49: ...47 9 2 3 Over current protection occurs 4 times diagnosis and solution ...
Страница 51: ...49 9 2 6 Indoor outdoor units communication error diagnosis and solution ...