35
A: The compressor keeps running for 40 minutes or more.
B: The temperature difference of evaporator and room temperature meets one of the following
Fan speed
T2-T1
Note
High
TH
DEFROST
If indoor fan is in high speed and T2-T1< TH
DEFROST
, start defrosting
Medium
TM
DEFROST
If indoor fan is in medium speed and T2-T1< TM
DEFROST
, start defrosting
Low
TL
DEFROST
If indoor fan is in low speed and T2-T1< TL
DEFROST
, start defrosting
Breeze or stop
/
If indoor fan is breezing or stopped, start defrosting
Calculate from the end of latest defrost, evaporator high temp. Protection only closes outdoor fan
with the compressor still running add up to 90 minutes.
2) Condition of ending defrosting:
If any one of the following items is satisfied, the defrosting will terminate and the machine will turn to
normal heating mode.
(1) The defrosting time is reached to the setting value.
(2) The compressor current reaches or exceeds
DEFROST
for 7 seconds.
3) Defrosting action
During the defrosting mode, if the machine stopped or transferred to other mode, the defrosting mode
will stop, and all the defrosting conditions will be cleared.
Содержание Oasis WOE10C2DB1 / HOE10C2MR83
Страница 10: ...8 Model W H D WOE10C2DB8 710 250 189 WOE13C2DB8 790 275 196 WOE18C2DB8 930 275 198 WOE24C2DB8 1036 315 230 ...
Страница 14: ...12 5 Wiring Diagram 5 1 Indoor Units WOE10C2DB8 WOE13C2DB8 WOE18C2DB8 WOE24C2DB8 ...
Страница 15: ...13 5 2 Outdoor Units HOE10C2MR83 HOE13C2MR83 HOE18C2MR83 ...
Страница 16: ...14 HOE24C2MR83 ...
Страница 46: ...44 9 2 Diagnosis and Solution 9 2 1 Indoor fan speed has been out of control diagnosis and solution ...
Страница 48: ...46 9 2 2 Open circuit or short circuit of temperature sensor diagnosis and solution ...
Страница 49: ...47 9 2 3 Over current protection occurs 4 times diagnosis and solution ...
Страница 51: ...49 9 2 6 Indoor outdoor units communication error diagnosis and solution ...