INSTALLATION
12 - 13:
ON/OFF contact for remote activation/deactivation
of the appliance.
• Operation must be activated by parameter
PF4
(see Con-
trol Panel manual).
Relay output terminals
14 - 16:
PV1 relay with 12 VDC 500 mW coil for connecting
to the plant/domestic hot water diverter valve.
15 - 16:
PP3 relay with 12 VDC 500 mW coil for secondary
pump connection.
If at least one relay output is used, the Control Pan-
el cannot be supplied by the heat pump but must be
supplied separately.
Support generator terminals
17 - 18:
BC1 normally open potential-free contact for back-
up heat generator. Maximum contact rating 1 A 230
VAC or 2 A 30 VDC (resistive load).
Check the tightness of all power conductor terminals at
first start-up and 30 days after commissioning.