41
INSTALLATION
– replace the rubber gasket
– fix the cables with the cable clamp
– close the electrical panel again
Make sure that the rubber gasket is correctly positioned
before closing the panel.
The power cable must be sized according to this manual.
Use a double-insulated multi-core cable mod. H07RNF for
outdoor applications in cable duct, or mod, H05VVF for in-
door applications.
Single-phase unit terminal block
H+ L-
serial connection with Control Panel for M1 monoblock versions or with indoor unit for H1 version
V+ V-
Control Panel power supply to be used only if no relay output on the terminal board of the control is used
SE
Disconnect switch (not supplied)
230V AC
Unit power supply
PE N
H L
L
V+ V-
L
N
230V AC
SE
V+
V–
H+
L–
<
<
<
<
Three-phase unit terminal block
V+ V-
Control Panel power supply to be used only if no relay output on the terminal board of the control is used
H+ L-
serial connection with Control Panel for M1 monoblock versions or with indoor unit for H1 version
SE
Disconnect switch (not supplied)
400V AC
Unit power supply
PE N
H L
L1 L2 L3
V+ V-
L1 L2 L3
N
400V AC
SE
V+
V–
H+
L–
<
<
<
<