54
Installation
Fire detection and extinguishing system
4.4
Mounting the internal modules
The internal modules (IFAMEVAC, IFAMAMP, IFAMIDANET, IFAMFFT, IFM24160,
IFM2L, IFM4R, IFM4IO, IFMDIAL, IFM16IO, IFMNET, IFMLAN, IFMEXT) must be
mounted in the special compartment inside the cabinet (
paragraph 3.2 - [L]
). There
are two bars on either side of the compartment for mounting and connecting
modules (
paragraph 3.2 - [J]
- [L]
), up to 8 per cabinet.
1.
Inside the compartment, find the position of the module that corresponds to
one of the connectors on the PCB bar (
paragraph 3.2 - [P]
).
If you are installing an IFM24160 power-supply module, you must use the first
connector at the top (
paragraph 3.2 - [U]
). When installing any other type of
internal module, you can use this or any other connector that is free
(
paragraph 3.2 - [V]
).
2.
Position the module in such a way that it is on level with the desired connector
on the bar hen insert it in place by pushing it carefully to the left.
3.
Affix the module to one of the holes on the grounding bar (
paragraph 3.2 - [L]
)
using one of the supplied screws.
4.
Complete the wiring on the internal module (refer to
paragraph 4.6.1 Cable
entry
and the paragraphs regarding the wiring of each internal module).