14
General Description
Fire detection and extinguishing system
2.6
Control Panels in an IP network
Multiple control panels, or networks of control
panels with fire functions, or IDANet networks of control
panels with fire and voice functions, can be connected to
each other via a TCP-IP connection.
Each node in a connection of this type is identified as a
“cluster”. Each cluster can consist of:
• a single control panel
• a repeater
• a network
• a IDANet network
• a network consisting of a ring and an
IDANet ring
By means of a TCP-IP connection, it is then possible to
connect several clusters together.
For further information regarding the method used for connecting control panels in a network refer to the Networking
Guide available at www.inim.biz
Attention:
The control panel that acts as a gateway for TCP-IP networking must include the FPMCPU module.
2.7
Inim Cloud fire
The INIM Electronics Cloud service provides Previdia system users with a
further method of intrusion panel management via Internet.
The connection of the control panels to the Cloud service is achieved via the
Ethernet connection of the IFMLAN module and access for the user is
possible with a web interface (App or any browser) without the need to
configure the network on which the control panel is installed. In particular, it
is not necessary to program a router to perform port-forwarding and the like
in order to reach the control panel.
Each cluster, equipped with at least one FPMCPU control panel, can be connected to the Inim cloud, allowing you to
take advantage of the following features:
• Remote system monitoring (thus overcoming local network configuration difficulties)
• System register management (in accordance with local regulations in force)
• Management of the maintenance register
2.8
List of Previdia Ultra system components
Following is a list of the elements available for the Previdia Ultra system:
• Standard models of Previdia Ultra control panels:
- Previdia-Ultravox
control panel in single cabinet with fire detection and voice evacuation functions
- Previdia-Vox
control panel in single cabinet with voice evacuation functions
- Previdia-Ultra216
control panel in single cabinet with fire detection functions
- Previdia-UltravoxR
control panel in single cabinet with fire detection and voice evacuation functions, in red
- Previdia-VoxR
control panel in single cabinet with voice evacuation functions, in red
- Previdia-Ultra216R
control panel in single cabinet with fire detection functions, in red
• Front-plate modules:
- FPMCPU
CPU / Repeater module
- FPAMIAS
Main control module for voice functions
- FPMLED
LED module
- FPMLEDPRN
LED module with printer
- FPMEXT
LED module for extinguishant module
- FPMNUL
Blind-plate module
LAN
Router
Internet