22
Wireless systems
Anti-intrusion control panels
The following table indicates the operating distances of the magnet in accordance with the
side used and the angles shown in the figure (these values have been calculated by
positioning the magnet in contact with the device, except for the angle y-, and with the
highest part of the contact cover aligned with that of the magnet cover):
3-1-4
Air2-FD100 smoke detector
The Air2-FD100 detector is capable of sensing the presence of smoke particles and thus
detecting a fire in its early stages.
Air2-FD100 optical smoke detector is equipped with a sampling chamber (based on light
scattering mass - Tyndall effect). In order to ensure the proper operating capacity of the
device, it must be installed away from drafts and large objects which may alter the airflow to
the sampling chamber.
ATTENTION!
The Air2-FD100 smoke detector that can be used exclusively for the detection of smoke in the
protected area. Therefore, in no way can an Air2-FD100 smoke detector be considered a fire
control system.
The operating parameters of detectors can be changed and adapted to the environmental
conditions, either from the control panel or via the programming software. The detector
signals alarm status when the level of smoke in the protected environment reaches the
following levels:
• 0.08 dB/m (pre-set mode)
• 0.10 dB/m
• 0.12 dB/m
• 0.15 dB/m
Table 3-11: Distance between magnet and contact (mm)
Axis
Contact long side
Contact short side
Near
Withdrawn
Near
Withdrawn
x +/-
11
9
15
14
y -
28
24
27
23
z +/-
40
35
37
33
EN 50131-1
EN 50131-5-3
EN 50130-4
EN 50130-5
INCERT
CEB T031
Table 3-12: Air2-FD100 technical specifications
Battery
type
Lithium CR17450 3V
estimated life
3 years
“Low battery” fault voltage
Less than 2.4V
Current draw
during standby
70
μ
A
maximum
Max 40mA
Operating environmental
conditions
temperature
from -10 to +40°C
relative humidity
93% without condensation
Height (base included)
60mm
Diameter (base included)
114mm
Weight
(base and battery included)
182 gr
Security rating
2
Environmental class
II