9. Connecting the consumption grid
This chapter explains the requirements and process for connecting the consumption grid wiring to the unit. Read
carefully before starting the connection process.
9.1. Safety instructions for connecting to the consumption grid
Before you start to make the connections, make sure there is no voltage in the inverter. Check that
the AC protection of the auxiliary grid/genset and the DC switch are open.
Do not switch on the power
to the unit until you have successfully made the rest of the connections
and the unit is closed.
9.2. Wiring requirements for connecting to the consumption grid
The wiring gauge for connecting the consumption grid is specified in the following table:
INGECON SUN STORAGE 1Play
Consumption grid wiring gauge
4 ~ 16 mm
2
Cable diameter
9 ~ 17 mm
9.3. Consumption grid connection process
To connect the consumption grid:
L
Live
N
Neutral
Ground
1.
Loosen the packing gland marked
LOADS
(see section
“2.7. Description of wiring inlets”
and pass the consumption grid cable through it.
2.
Open the clamp-type terminals
J56
LOADS
, insert the respective cables respecting the polarity and close
said terminals. Ingeteam recommends using a tubular terminal in accordance with
DIN 46 228/1
.
3.
Correctly tighten the packing glands to prevent losses to the protection class, verifying that the wiring is
not taut. Check that the connection is tight.
The consumption grid neutral is not internally connected to ground.
76
Connecting the consumption grid
Ingeteam
ABH2013IQM01_A - Installation and Operation Manual
Содержание INGECON SUN STORAGE 1Play 3
Страница 3: ...3 Ingeteam ABH2013IQM01_A Deutsch DE English EN Espa ol ES Fran ais FR Italiano IT Portugu s PT...
Страница 305: ...Anmerkungen Notes Notas Remarques Note Notas...
Страница 306: ...Anmerkungen Notes Notas Remarques Note Notas...
Страница 308: ...Ingeteam Power Technology S A www ingeteam com ABH2013IQM01_A 11 2016...