Parameter
Explanation
VNOMINAL
Storage system rated voltage (V).
CAPACITY
Storage system (C20) capacity, in Ah.
I CHARGE
Maximum storage system charge current, in amps.
I DISCHARGE
Maximum storage system discharge current, in amps.
TEMP. COMP.
Storage system voltage compensation constant as a function of temperature (V/ºC).
V ABSORPTION
Storage system absorption voltage (V).
V FLOTATION
Storage system flotation voltage (V).
V EqUALIzATION
Storage system equalization voltage (V).
T ABSORPTION
Duration of absorption charge, in minutes. Time for which the storage system must be
maintained at the absorption voltage.
T EqUALIzATION
Duration of equalization charge, in minutes. Time for which the storage system must be
maintained at the equalization voltage.
N.EqU. CYCLES
Number of cycles to carry out an automatic equalization.
20.7.2. Inverter
From this menu the parameters of the inverter/charger can be set.
Parameter
Explanation
RMS VOLTAGE
RMS voltage generated (V).
FREqUENCY
Frequency of generated voltage (Hz).
AC PHASE
Phase (R, S, T or single phase) to be generated by the inverter. The single phase will be
configured by default.
20.7.3. Grid/Genset
Type of grid
This menu is for selecting and configuring the type of auxiliary grid/genset input to be used in the installation.
The
>
symbol points to the option selected. To select the desired option and configure it, press
on the option
once it is highlighted.
If the option selected is
GENERATOR
, the following parameters must be set:
Parameter
Explanation
RATED POWER
Auxiliary generator rated power, in watts. Obtain this information from the generator
manufacturer.
VAC MIN
Minimum AC voltage of the generator, in volts. Obtain this information from the generator
manufacturer.
VAC MAx
Maximum AC voltage of the generator, in volts. Obtain this information from the generator
manufacturer.
FAC MIN
Minimum AC frequency of the generator (Hz).
FAC MAx
Maximum AC frequency of the generator (Hz).
If the option selected is
GRID
, the country in which the unit is installed must be set.
By default the voltage and frequency values are set in accordance with the standards in the selected country.
Should these values be modified, Ingeteam accepts no liability for any consequences which may occur as a result
of this modification.
Manual connection
Allows the inverter to be manually connected to the auxiliary grid/genset immediately. The unit will continue to run
until the shut-down is ordered by the same method.
95
Display control
Ingeteam
ABH2013IQM01_A - Installation and Operation Manual
DE
EN
ES
FR
IT
PT
Содержание INGECON SUN STORAGE 1Play 3
Страница 3: ...3 Ingeteam ABH2013IQM01_A Deutsch DE English EN Espa ol ES Fran ais FR Italiano IT Portugu s PT...
Страница 305: ...Anmerkungen Notes Notas Remarques Note Notas...
Страница 306: ...Anmerkungen Notes Notas Remarques Note Notas...
Страница 308: ...Ingeteam Power Technology S A www ingeteam com ABH2013IQM01_A 11 2016...