6.4. Protection of the connection to the consumption grid
Thermomagnetic circuit breaker
It is possible to install a thermomagnetic circuit breaker and/or fuse on the connection between the inverter and
the consumption grid.
The following table provides the necessary data for the selection of these devices by the installer.
INGECON SUN STORAGE 1PLAy
Maximum inverter
current
Rated current for the
type-B thermomagnetic
circuit breaker
3 / 3TL
13 A
20 A
6 / 6TL
26 A
32 A
You must take into account when selecting the protection that the ambient working temperature influences the
maximum current permitted by these protections as indicated by the manufacturer.
Residual current device
You must comply with applicable regulations governing the protection of people in the consumption grid.
6.5. Protection of the connection to the auxiliary grid/genset
It is possible to install a thermomagnetic circuit breaker and/or fuse on the connection between the inverter and
the auxiliary grid/genset.
The following table provides the necessary data for the selection of these devices by the installer.
INGECON SUN STORAGE 1PLAy
Maximum auxiliary
grid/genset current
Rated current for the
type-B thermomagnetic
circuit breaker
3 / 3TL
50 A
63 A
6 / 6TL
50 A
63 A
70
Preparation for installing the unit
Ingeteam
ABH2013IQM01_A - Installation and Operation Manual
Содержание INGECON SUN STORAGE 1Play 3
Страница 3: ...3 Ingeteam ABH2013IQM01_A Deutsch DE English EN Espa ol ES Fran ais FR Italiano IT Portugu s PT...
Страница 305: ...Anmerkungen Notes Notas Remarques Note Notas...
Страница 306: ...Anmerkungen Notes Notas Remarques Note Notas...
Страница 308: ...Ingeteam Power Technology S A www ingeteam com ABH2013IQM01_A 11 2016...