Do not touch boards or electronic components. The more sensitive components can be damaged or
destroyed by static electricity.
Do not disconnect or connect any terminal while the unit is operating. Disconnect and check for
absence of voltage first.
3.2. Personal Protective Equipment (PPE)
When working on the unit, use the following safety equipment recommended by Ingeteam as a minimum.
Name
Explanation
Safety footwear
In compliance with standard
UNE-EN-ISO 20345:2012
Helmet
In compliance with standard
EN 397:2012 + A1:2012
Helmet with face shield
In compliance with Standard
UNE-EN 166:2002
, wherever there are directly
accessible live parts.
Safety goggles
In compliance with standard
UNE-EN 166:2002
Working clothes
Close-fitting, non-flammable, 100% cotton
Dielectric gloves
In compliance with standard
EN 60903:2005
Tools and / or equipment used in live work must have at least Category III-1000 Volts insulation.
Should the country’s regulations demand another kind of personal protection, you should appropriately supplement
the equipment recommended by Ingeteam.