INSTALLATION / HANDLING
19
SSR UP6 40, SSR UP6 50PE, SSR UP6 50PEI, HF50–PE, EP50–PE,
HP50–PE, HXP50–PE
ELECTRICAL DATA – ALL UNITS SSR UP6–40–HA
Standard voltage
200V
230V
380V
460V
575V
PACKAGE
Motor enclosure
ODP
TEFC
ODP
TEFC
ODP
TEFC
ODP
TEFC
ODP
TEFC
Power (nominal)
40HP
Full load current at maximum
pressure
136.0A
128.3A
119.0A
111.5A
71.6A
65.1A
59.5A
56.9A
47.6A
44.7A
Full load current at maximum
pressure with dryer option
–
–
123.5A
116.0A
–
–
61.7A
58.1A
–
–
Starting current FV (STAR)
706 (265)
617 (231)
374 (140)
309 (115)
247 (93)
Starting current FV (STAR)
with dryer option
–
652 (268)
–
323 (131)
–
Starting time FV (STAR)
3–5 Sec (7–10 Sec)
Starts per hour (maximum)
6
ELECTRICAL DATA – FV / Star Delta
Control voltage
120VAC
Minimum fuse rating
See note 1
175A
150A
90A
75A
60A
Minimum fuse rating with dryer
option
See note 1
–
–
175A
150A
–
–
80A
75A
–
–
Minimum wire size AWG
See note 2
4/0
3/0
2
3
4
ELECTRICAL DATA – ALL UNITS SSR 30E–HA
Standard voltage
200V
230V
380V
460V
575V
PACKAGE
Motor enclosure
ODP
TEFC
ODP
TEFC
ODP
TEFC
ODP
TEFC
ODP
TEFC
Power (nominal)
30HP
Full load current at maximum
pressure
109.2A
100.9A
95.0A
87.8A
57.5A
53.1A
47.5A
43.9A
38.0A
38.3A
Full load current at maximum
pressure with dryer option
–
–
99.5A
92.3A
–
–
49.7A
46.1A
–
–
Starting current FV (STAR)
567 (212.4)
493.2 (184.8)
298.5 (111.8)
246.6 (92.4)
197.3 (73.9)
Starting current FV (STAR)
with dryer option
–
516.6 (193.5)
–
258 (96.7)
–
Starting time FV (STAR)
3–5 Sec (7–10 Sec)
Starts per hour (maximum)
6
ELECTRICAL DATA – FV / Star Delta
Control voltage
120VAC
Minimum fuse rating
See note 1
150A
125A
125A
125A
75A
75A
60A
60A
50A
50A
Minimum fuse rating with dryer
option
See note 1
–
–
150A
150A
–
–
75A
75A
–
–
Minimum wire size AWG
See note 2
3/0
1/0
3
4
6