INSTALLATION / HANDLING
18
SSR UP6 40, SSR UP6 50PE, SSR UP6 50PEI, HF50–PE, EP50–PE,
HP50–PE, HXP50–PE
ELECTRICAL DATA – ALL UNITS SSR UP6–40
Standard voltage
200V
230V
380V
460V
575V
PACKAGE
Motor enclosure
ODP
TEFC
ODP
TEFC
ODP
TEFC
ODP
TEFC
ODP
TEFC
Power (nominal)
40HP
Full load current at maximum
pressure
136.0A
125.6A
118.3A
109.2A
71.6A
66.1A
59.2A
54.6A
47.3A
43.7A
Full load current at maximum
pressure with dryer option
143.7A
133.3A
125.2A
116.1A
–
–
62.5A
57.9A
–
–
Starting current FV (STAR)
706.1 (264.5)
614 (230)
367 (135.2)
307 (115)
245.6 (92)
Starting current FV (STAR)
with dryer option
744.4 (302.5)
652 (268)
–
323 (131)
–
Starting time FV (STAR)
3–5 Sec (7–10 Sec)
Starts per hour (maximum)
6
ELECTRICAL DATA – FV / Star Delta
Control voltage
120VAC
Minimum fuse rating
See note 1
175A
150A
100A
90A
75A
60A
Minimum fuse rating with dryer
option
See note 1
200A
175A
175A
150A
–
–
80A
75A
–
–
Minimum wire size AWG
See note 2
4/0
3/0
2
3
4
ELECTRICAL DATA – ALL UNITS SSR UP6 50PE, UP6 50PEI, HF50–PE, EP50–PE, HP50–PE and HXP50–PE
Standard voltage
200V
230V
380V
460V
575V
PACKAGE
Motor enclosure
ODP
TEFC
ODP
TEFC
ODP
TEFC
ODP
TEFC
ODP
TEFC
Power (nominal)
50HP
Full load current at maximum
pressure
170.8A
160.0A
148.5A
139.1A
89.8A
82.2A
74.2A
67.9A
59.4A
55.7A
Full load current at maximum
pressure with dryer option
–
–
155.4A
146.0A
–
–
77.5A
71.2A
–
–
Starting current FV (STAR)
876.3 (321.2)
762 (279.3)
461 (169.0)
381 (139.7)
304.8 (111.7)
Starting current FV (STAR)
with dryer option
–
800 (317)
–
397 (156)
–
Starting time FV (STAR)
3–5 Sec (7–10 Sec)
Starts per hour (maximum)
6
ELECTRICAL DATA – FV / Star Delta
Control voltage
120VAC
Minimum fuse rating
See note 1
225A
200A
200A
175A
110A
110A
100A
90A
75A
70A
Minimum fuse rating with dryer
option
See note 1
–
–
200A
200A
–
–
100A
90A
–
–
Minimum wire size AWG
See note 2
250
4/0
1
2
3