29
XtrapulsCD1-pm
– Installation manual
Chapter 4 - Connections
1.4
– CONNECTION OF A BACKUP BATTERY FOR THE 24 VDC AUXILIARY SUPPLY
The Xtrapuls CD1-pm positioner consumption is 320 mA with 24 V
DC
. So, a 24 V / 30 A/h battery can keep the
positioner under voltage during i.e. a long 3 days week-end or during a mains cut-off without losing the machine
initialization. This backup method is very interesting for saving the machine initialization as well as the axis
position even when moving with mains switched off. An ASCII command allows sending the axis position to the
digital host system.
1.5
– CONNECTION EXAMPLE FOR A MULTIAXIS APPLICATION