Chapter 3 - Inputs-Outputs
XtrapulsCD1-pm
– Installation manual
10 - X9: POWER CONNECTOR: MAINS, MOTOR, BRAKING RESISTOR (CD1-pm-230 V & 400 V)
Xtrapuls CD1-pm-230/I: 10 pins male connector (with 5.08 mm pitch). Female connector supplied.
Xtrapuls CD1-pm-400/I: 10 pins male connector (with 7.62mm pitch). Female connector supplied.
Xtrapuls CD1-pm-400/70 and 90: 10 pins male connector (with 10.16 mm pitch).
Female connectors supplied in 2 parts: 7 pins female, pins 1 to 7 and 3 pins
female, pins 8 to 10 for the motor.
Fastening torque of the connector screws: 0.5 Nm
PIN
SIGNAL
I/O
FUNCTION
DESCRIPTION
1
RB
O
Power feedback during the motor
deceleration with high inertia and
speed
CD1-pm-230/I: 100 Ohms/100 W
(dp 100/100)
CD1-pm-400/1.8 to 7.2: 200 Ohm/100 W
(dp 200/100)
CD1-pm-400/14: 50 Ohm/200 W
(dp 50/200)
CD1-pm-400/30/45: 33 Ohm/280 W
(dp 33/280)
CD1-pm-400/70 and 90: 16.5 Ohm/560 W
(dp 16.5/560)
(Braking resistors must be separately ordered)
2
RB
O
3
DC-
I/O
Parallel connection of the DC bus Only on UL listed items.
4
L1
I
Mains input
CD1-pm-230/I 230 V
AC
1~ or 3~
CD1-pm-400/I 400 to 480 V
AC
3~
5
L2
I
6
L3
I
7
DC+
I/O
Parallel connection of the DC bus Only on UL listed items.
8
W
O
Motor phase W
Motor cable with grounded connection by means
of Faston socket and 360° shield connection on
grounded collar
9
V
O
Motor phase V
10
U
O
Motor phase U
IMPORTANT: The motor and brake cable must be shielded and connected over 360° on collars mounted for this
purpose on the housing. The ground wire of the motor cable MUST be connected to the Faston socket marked
with the GND sign.
The earth reference must also be connected on the second Faston socket.
▪
The installer of the drives has to use a UL Listed Quick connect for ground connection (0.250 inches or
6.35 mm wide nominal).
▪
Field wiring terminals have to use copper conductors only.
Torque value for field wiring terminals: value to be according to the Recognized terminal block used.