Addr
Inst
R/W
Host
R/W
Range Description
40117
R
R/W
MSB=$01 to $0C,
LSB=$01 to $1F
RTC Month and Day
Holds the month and day to which the real time
clock (RTC)
calendar should be set. The most
significant byte (MSB) represents the month
from $01 to $0C (1-12). The least significant
byte (LSB) represents the day of the month
from $01 to $1F (1-31).
Examples:
December 25 = $0C19
June 31
= $061F
40118
R
R/W
$0002 to $0063
RTC Year (00yy)
Holds the year to which the real time clock
(RTC) should be set. The most significant byte
(MSB) is always $00. The least significant byte
(LSB) represents the two-digit year (within the
21
st
century), from $02 (which represents 2002)
to $063 (which represents 2099).
Examples:
2002 = 02 (+ base year of 2000)
= $0002
2010 = 10 (+ base year of 2000) = $000A
2099 = 99 (+ base year of 2000)
= $0063
40119
R
R/W
MSB=$00 to $18,
LSB=$00 to $3C
RTC Hours and Minutes
Holds the hours and minutes to which the RTC
should be set. The most significant byte (MSB)
represents the hour from $00 to $18 (00-24).
The least significant byte (LSB) represents the
minutes from $00 to $3C (00 to 60). Note that
the seconds default to zero ($00) each time the
hours and minutes are set.
Examples:
13:05 = $0D05
24:00 = $1800
40124
R
R/W
$0000 to $FFFF
Low Alarm Display Setting
Holds the value of the gas reading at which the
low alarm display will activate.
40125
R
R/W
$0000 to $FFFF
High Alarm Display Setting
Holds the value of the gas reading at which the
high alarm display will activate.
Содержание iTrans 77023554
Страница 10: ...List of Tables iTrans Fixed Point Single Dual Gas Monitor x INDUSTRIAL SCIENTIFIC P N 77023554 ...
Страница 16: ......
Страница 42: ...System Wiring iTrans Fixed Point Single Dual Gas Monitor 4 18 INDUSTRIAL SCIENTIFIC P N 77023554 ...
Страница 86: ...Appendix D iTrans Fixed Point Single Dual Gas Monitor D 2 INDUSTRIAL SCIENTIFIC P N 77023554 ...
Страница 88: ...Appendix E iTrans Fixed Point Single Dual Gas Monitor E 2 INDUSTRIAL SCIENTIFIC P N 77023554 ...
Страница 94: ...Index iTrans Fixed Point Single Dual Gas Monitor vi INDUSTRIAL SCIENTIFIC P N 77023554 ...