System Wiring
iTrans Fixed Point Single/Dual Gas Monitor
4-2
INDUSTRIAL SCIENTIFIC
(P/N: 77023554)
6.
Shielding from either the controller or remote sensors should be bonded to the
enclosure screw located inside the
.
IMPORTANT:
Use of this product in areas where it may be subject to large
amounts of electromagnetic interference may affect the reliable operation of this
device and should be avoided.
WARNING:
Supply wire with a minimum rating of 90C must be used for
interconnection to the
.
NOTE:
For classified locations, a “poured” wire seal must be installed within
18 inches of the main unit for both power entry and remote sensors.
NOTE:
Remove power from the
before making any wiring connections.
4.3. Alarm Relay Wiring (J1, J5, and J6)
To connect the
control wires to the three relay terminals on the relay
board, wire the unit to the connectors shown in Figure 4-2.
The
low alarm relay
is activated when the low alarm threshold is met. This is a non-latching, Normally
Open (NO) contact. See Figure 4-1. The
high alarm relay
is activated when the
high alarm threshold is met. This is a non-latching, Normally Open (NO) contact.
See Figure 4-1. The
fault alarm relay
is activated when a fault condition occurs.
This is a non-latching, Normally Closed (NC) contact. When a fault condition is
met, the circuit opens. Refer to Figure 4-3.
NOTE:
It is recommended that on-board relays should not be used to drive loads
directly. On-board relays should be used to drive a secondary, higher-power relay
which is connected to the control device (e.g., strobe, siren, exhaust fan, etc.).
Figure 4-1. High and Low Alarm Relay Connectors J6 and J5
Содержание iTrans 77023554
Страница 10: ...List of Tables iTrans Fixed Point Single Dual Gas Monitor x INDUSTRIAL SCIENTIFIC P N 77023554 ...
Страница 16: ......
Страница 42: ...System Wiring iTrans Fixed Point Single Dual Gas Monitor 4 18 INDUSTRIAL SCIENTIFIC P N 77023554 ...
Страница 86: ...Appendix D iTrans Fixed Point Single Dual Gas Monitor D 2 INDUSTRIAL SCIENTIFIC P N 77023554 ...
Страница 88: ...Appendix E iTrans Fixed Point Single Dual Gas Monitor E 2 INDUSTRIAL SCIENTIFIC P N 77023554 ...
Страница 94: ...Index iTrans Fixed Point Single Dual Gas Monitor vi INDUSTRIAL SCIENTIFIC P N 77023554 ...