iTrans Fixed Point Single/Dual Gas Monitor
ModBus Interface
(P/N: 77023554)
INDUSTRIAL SCIENTIFIC
6-1
M
OD
B
US
I
NTERFACE
Chapter
6
6.1. Introduction
When programming the ModBus ID address on the
electronics module
or on the smart sensor board, use the binary reference chart on the following page.
A “1” represents “ON” on the switch bank, and position 1 of the switch bank
represents the right most binary digit (LSB).
ModBus characteristics for the
are listed below.
Table 6-1. ModBus Characteristics for the
Gas Monitor
Characteristic Description
Hardware
2-wire mode (not 4-wire)
Baud Rate
9600
Electrical Standard
TIA/EIA-485
Transmission Mode
RTU mode (not ASCII)
Message Coding System
8-bit
Start Bits
1
Data Bits
8 (LSB sent first)
Parity Bits
0
Stop Bits
1
Important:
When commissioning master and slave units on a ModBus network, it
is critical to ensure that every device on the ModBus network must have a unique
address. Otherwise, abnormal behavior of the entire serial bus can occur.
6.2. Sample Gas Reading via ModBus Network
To get a gas reading for an individual sensor, you must read register 40102. This
register holds the gas reading in ppm.
Содержание iTrans 77023554
Страница 10: ...List of Tables iTrans Fixed Point Single Dual Gas Monitor x INDUSTRIAL SCIENTIFIC P N 77023554 ...
Страница 16: ......
Страница 42: ...System Wiring iTrans Fixed Point Single Dual Gas Monitor 4 18 INDUSTRIAL SCIENTIFIC P N 77023554 ...
Страница 86: ...Appendix D iTrans Fixed Point Single Dual Gas Monitor D 2 INDUSTRIAL SCIENTIFIC P N 77023554 ...
Страница 88: ...Appendix E iTrans Fixed Point Single Dual Gas Monitor E 2 INDUSTRIAL SCIENTIFIC P N 77023554 ...
Страница 94: ...Index iTrans Fixed Point Single Dual Gas Monitor vi INDUSTRIAL SCIENTIFIC P N 77023554 ...