Configuration options, Table C:

Independent configurations. These configurations can be changed independently of the switch position on the ASD 533. 

Sector

Parameter

Default

Setting

Selection

Time

Year, month, day, hour, minute

---

minutes – year

Relay / OC output / reset key / various

Relay 3 and OC output 3, AMB 33

freely programmable

in accordance with

Configuration options

relay allocation

” 

Relay 1, 1

st

RIM 35

Pre-signal 1

Relay 2, 1

st

RIM 35

Pre-signal 2

Relay 3, 1

st

RIM 35

Pre-signal 3

Relay 4, 1

st

RIM 35

Smoke sensor dirty

Relay 5, 1

st

RIM 35

Pipe blockage sampling pipe

Relay 1, 2

nd

RIM 35

freely programmable

Relay 2, 2

nd

RIM 35

Relay 3, 2

nd

RIM 35

Relay 4, 2

nd

RIM 35

Relay 5, 2

nd

RIM 35

Reset key On / Off

On

On / Off

Heating control, subsequent heating time

2 min

1 – 60 min

MCM setting, recording interval

1 s

1 – 120 s

MCM smoke peak value memory

Off

Off / On

Carry out new initial reset

---

On / Off

Smoke sensor mode of operation (smoke sensor I)

SSD/DMB

SSD/DMB or OEM inputs

(individual or in combination)

Switched off

Isolate smoke sensor (smoke sensor I)

Normal operation

Isolate / normal operation

Filter monitoring (smoke sensor I)

Off

Off / On

Filter service life

6 months

1 – 24 months

Read out operation time

---

months / days

Filter replacement

---

start / finish

Relay allocation configuration options:

The following criteria can be programmed on a maximum of 11 relays (1 AMB 33 unit with ASD 533-1 and ASD 535-3, 5 units with 1

st

RIM 35, 

5 units with 2

nd

RIM 35):

Smoke sensor / LS-Ü

General

Smoke sensor alarm

Fan fault

Pre-signal 1

Operating voltage fault

Pre-signal 2

Initial reset fault

Pre-signal 3

Lithium battery / clock fault

Smoke sensor dusty

Smoke sensor soiled

Smoke sensor fault

Pipe blockage sampling pipe

Pipe breakage sampling pipe

Heating control

Alarm 2

The criteria can also be allocated using the OR function (e.g. smoke sensor dust or soiling together on one relay).

Содержание ASD 533

Страница 1: ... 35 Memory Card Module The ASD 533 can be connected to a higher level FACP via poten tial free change over contacts Fitting an XLM 35 or SLM 35 means that the ASD 533 can be ide ally connected to the SecuriFire and Integral fire alarm systems via the addressable loop with SLM also to the SecuriPro The RIM 35 is available as a further installation option This mod ule enables the availability of all...

Страница 2: ...allation of the ASD release the two lock clamps however it should be left inside its protective packaging until the definitive commissioning The definitive installation is carried out as de scribed below see Fig 3 Always leave the smoke sensor inside its protective packaging until it is ready to be installed definitively in the detector housing Depending on the circumstances e g long period of tim...

Страница 3: ...manently assigned parameters Normative system limits according to EN 54 20 Class A to C positions A11 to C31 Non normative system limits positions W01 to W44 Configurable positions for settings after using ASD PipeFlow and or ASD Config or SecuriPro SecuriFire or Integral FACP SLM 35 XLM 35 X01 to X03 The parameters are saved at the factory with values for compliance with EN 54 20 Changing the par...

Страница 4: ...ior consultation with the manufacturer The airflow monitoring values stored under those switch positions are not tested in accordance with EN For more information on using the table of system limits please refer to the Technical description T 140 287 Sec 4 4 4 3 and 4 4 4 4 Table of system limits for planning without ASD PipeFlow calculation Compliant with EN 54 20 Class A highly sensitive Shape S...

Страница 5: ... 5 3 0 7 0 11 2 0 2 0 2 0 2 0 2 5 2 5 2 5 2 5 2 5 4 0 7 0 12 2 0 2 0 2 0 2 0 2 0 2 0 2 5 2 5 2 5 2 5 4 0 7 0 U T shaped sampling pipes Number of sam pling holes per sampling branch Hole diameter in mm for the sampling hole number as of ASD 1 2 3 4 5 6 7 8 1 5 0 2 4 0 5 0 3 4 0 4 0 5 0 4 4 0 4 0 4 0 5 0 5 4 0 4 0 4 5 5 0 6 5 6 3 0 3 0 3 5 3 5 4 0 6 5 7 2 5 3 0 3 0 3 5 3 5 4 0 6 5 8 2 5 2 5 3 0 3 0 ...

Страница 6: ... 5 60 5 X01 X03 Soiling threshold of Al 75 65 100 5 X01 X03 Dust latching On On Off X01 X03 Soiling latching On On Off X01 X03 Smoke sensor fault delay 30 s 0 s 60 s 1 s X01 X03 Airflow monitoring LS Ü pipe blockage On Off On On Off X01 X03 LS Ü pipe breakage On Off On On Off X01 X03 LS Ü sensitivity applies to A01 to C31 20 1 70 1 X01 X03 LS Ü value averaging number 20 1 30 1 X01 X03 LS Ü delay a...

Страница 7: ...al 1 s 1 120 s MCM smoke peak value memory Off Off On Carry out new initial reset On Off Smoke sensor mode of operation smoke sensor I SSD DMB SSD DMB or OEM inputs individual or in combination Switched off Isolate smoke sensor smoke sensor I Normal operation Isolate normal operation Filter monitoring smoke sensor I Off Off On Filter service life 6 months 1 24 months Read out operation time months...

Страница 8: ... b21 Displays the new set ting Initial reset Measure Display Procedure remarks Before carrying out an initial reset i e after switching on the ASD 533 make sure you observe a waiting time of at least 5 min 1 Press the UP key flashing C31 or others Displays the default setting or the installa tion specific switch position 2 Press the UP key several times until dis play shows U in succession A to U ...

Страница 9: ...200006 01 XX SecuriLine eXtended line module XLM 35 11 2200003 01 XX SecuriLine module SLM 35 4000286 0101 Relay interface module RIM 35 4000287 0101 Memory card module MCM 35 4000285 0101 SD memory card industrial version 11 4000007 01 XX USB cable 4 5 m 4301248 Main board AMB 33 1 11 2200004 01 XX BCB 35 without smoke level indicator 4301220 0101 Aspirating fan unit AFU 35 complete 4000299 Airfl...

Страница 10: ... C Sampling pipe temperature range 20 60 C Max permissible temperature fluctuation in detector housing and sampling pipe operation 20 C Max permissible storage temperature for detector housing without condensation 20 70 C Ambient pressure difference between detector housing and sampling pipe sampling holes must be identical Humidity ambient condition for detector housing transient without condensa...

Отзывы: