Checking fault and alarm release
Test
Procedure
Action
Block or switch off the fire incident control and remote
alerting on superordinate FACP.
Check airflow
monitoring
Tape over the
sampling ho-
les (adhesive
tape); the
number de-
pends on the
pipe configu-
ration.
•
As soon as the resulting
change in airflow rate exceeds
±20% (which can also be
checked using switch position
V
), the “Fault” LED begins to
flash.
•
Once the LS-Ü delay (300 s)
has elapsed, the ASD triggers
a fault
fault on FACP
.
Check alarm
release
Impose
smoke at the
maintenance
sampling hole
or sampling
hole.
•
ASD triggers an alarm
alarm on FACP; check for cor-
rect alarm transmission (zone/
range release) on the FACP
.
•
Any pre-signals will also re-
lease.
Reset the ASD 533 between each check (please note: reset-
ting the ASD does not reset the FACP).
Alternatively, this control can also be performed using the “Test
trigger” function from
EasyConfig
switch position
I
.
Article numbers and spare parts
Short designation
Article number
Aspirating smoke detector ASD 533-1
11-2000001-01-XX
Replacement smoke sensor SSD 533
11-2200006-01-XX
SecuriLine eXtended line module XLM 35
11-2200003-01-XX
SecuriLine module SLM 35
4000286.0101
Relay interface module RIM 35
4000287.0101
Memory card module MCM 35
4000285.0101
SD memory card (industrial version)
11-4000007-01-XX
USB cable, 4.5 m
4301248
Main board AMB 33-1
11-2200004-01-XX
BCB 35 (without smoke level indicator)
4301220.0101
Aspirating fan unit AFU 35, complete
4000299
Airflow sensor AFS 35
4000300
Insect protection screen IPS 35 (set of 2)
11-2300012-01-XX
Lithium battery
11-4000002-01-XX
Cable screw union
M20 (set of 10)
11-4000003-01-XX
M25 (set of 10)
11-4000004-01-XX
Adapter US cable screw union AD US M-Inch 11-2300029-01-XX
Universal module support UMS 35
4301252.0101
Technical description ASD 533
T 140 287
Material for the sampling pipe
T 131 194
Commissioning protocol
T 140 299
Data sheets
XLM 35
T 140 088
SLM 35
T 131 197
RIM 35
T 131 196
MCM 35
T 131 195
AFU 35 installation instructions
T 131 200
Declaration of performance
www.securiton.ch/declaration-of-performance
Dimensioned drawing
Fig. 5 Detector housing dimensioned drawing
Position of M25
screwed cable glands
and air outlet
Position
of air outlet
Space requirement
for offset mounting
of the housing cover
for commissioning
and maintenance
27
(76)
27
35
22
148
57
23
(1
71
)
34
8
ca
. 2
6
(3
97
)
265
114
35
44
74
31
225
20
20
31
0
19
19
10 6,5