Configuration options, Table A:
The criteria below can be set separately with the day/night control activated. Configuration changes are saved on
X01
to
X03
.
Sector
•
Parameter
Default
Setting
Area
Resolution /
Levels
Saving after
change
Alarm 2
•
Alarm 2 On / Off
Off
Off / On
X01
–
X03
•
Sensitivity (always at least 20% above alarm)
1%/m
– 10%/m
0.0002%/m
X01
–
X03
•
Alarm 2 delay
2 s
0 s – 60 s
1 s
X01
–
X03
•
Alarm 2 latching
On
On / Off
X01
–
X03
•
Hold time for area switchover (Al 2 to Al)
20
10 – 250
1 s
X01
–
X03
Alarm (EN 54-20)
•
Alarm threshold
C11
0.02 – 10%/m
0.0002%/m
X01
–
X03
•
Smoke level value averaging (number)
4
1 – 10
1
X01
–
X03
•
Alarm delay (
UL/ULC max. 30 s
)
2 s
0 s – 60 s
1 s
X01
–
X03
•
Alarm cascading
Off
Off / On
X01
–
X03
•
Alarm latching
On
On / Off
X01
–
X03
Pre-signal
•
Pre-signal 1 On / Off
On
On / Off
X01
–
X03
•
Pre-signal 2 On / Off
On
On / Off
X01
–
X03
•
Pre-signal 3 On / Off
On
On / Off
X01
–
X03
•
Pre-signal 1 (100% = alarm threshold)
30%
10 – 90%
10%
X01
–
X03
•
Pre-signal 2 (100% = alarm threshold)
50%
VS
1 + 10 – 90%
10%
X01
–
X03
•
Pre-signal 3 (100% = alarm threshold)
70%
VS
2 + 10 – 90%
10%
X01
–
X03
•
Pre-signal delay (VS 1 – VS 3)
2 s
0 s – 60 s
1 s
X01
–
X03
•
Pre-signal latching
Off
Off / On
X01
–
X03
Smoke sensor dust/soiling
•
Smoke sensor dust On / Off
On
On / Off
X01
–
X03
•
Smoke sensor soiling On / Off
On
On / Off
X01
–
X03
•
Dust threshold (% of Al)
50%
5 – 60%
5%
X01
–
X03
•
Soiling threshold (% of Al)
75%
65 – 100%
5%
X01
–
X03
•
Dust latching
On
On / Off
X01
–
X03
•
Soiling latching
On
On / Off
X01
–
X03
•
Smoke sensor fault delay
30 s
0 s – 60 s
1 s
X01
–
X03
Airflow monitoring
•
LS-Ü pipe blockage On / Off
On
On / Off
X01
–
X03
•
LS-Ü pipe breakage On / Off
On
On / Off
X01
–
X03
•
LS-Ü sensitivity (applies to
A01
to
C31
)
±20%
±1 – ±70%
± 1%
X01
–
X03
•
LS-Ü value averaging (number)
20
1 – 30
1
X01
–
X03
•
LS-Ü delay (applies to
A01
to
C31
)
300 s
10 s – 3600 s
1 s
X01
–
X03
Stored under switch positions
W01
to
W44
are increased values which are
not
tested for EN compliance (see Technical descrip-
tion, T 140 287, Sec. 4.4.4.4).
Configuration options, Table B:
The following criteria apply to the entire ASD 533. Configuration changes are stored in connection with the adjustments from Table A, likewise
on one of the user configurable switch positions
X01
to
X03
.
Sector
•
Parameter
Default
Setting
Area
Resolution /
Levels
Saving after
change
Autolearning
•
Autolearning On / Off
Off
On
X01
–
X03
•
Autolearning duration
3 days
1 min to 14 days
min, h, days
X01
–
X03
•
Autolearning factor (of measured Al threshold)
1.5
1.1 – 10 x
X01
–
X03
Day/night control / weekday control
•
Day/night control On / Off
Off
Off / clock / FACP /
input “
OEM1
/
St
”
X01
–
X03
•
Day start time (only with “Clock”)
06:00
00:00 – 24:00
1 min
X01
–
X03
•
Night start time (only with “Clock”)
20:00
00:00 – 24:00
1 min
X01
–
X03
•
Weekday control (only with “Clock”)
On
Mon to Sun
Days
X01
–
X03
General faults
•
Lithium battery / clock fault
On
On / Off
X01
–
X03
Deactivate / switch off sensor
•
Smoke sensor I
On
On / deactivated
X01
–
X03